Specifications – Det-Tronics U5006 Air Duct Smoke Detector User Manual

Page 2

Advertising
background image

95-8456

2.2

2

SPECIFICATIONS

OPERATING VOLTAGE—

20 to 28 Vdc filtered supply, with less than 1.4 vpp at

60 to 120 Hz.

OPERATING CURRENT—

Standby: 10 milliamperes.

Alarm:

50 milliamperes.

TEMPERATURE RANGE—

Operating: –13°F to +140°F (–25°C to +60°C).

Storage: –67°F to +185°F (–55°C to +85°C).

HUMIDITY RANGE—

0 to 90% RH non-condensing.

AIR VELOCITY RANGE—

600 to 4000 ft/min.

SENSITIVITY RANGE—

Meets ANSI/UL268A visible smoke obscuration limits:

Grey smoke: 4.0%/ft maximum, 0.5%/ft minimum

Black smoke: 10.0%/ft maximum, 0.5%/ft minimum.

ALARM AND SUPERVISORY RELAY CONTACT
RATING—

1.0 ampere at 30 Vdc, SPST.

AUXILIARY ALARM RELAY CONTACT RATING—

2.0 amperes at 30 Vdc, Form C, SPDT.

JUNCTION BOX—

Body material: Aluminum.

Conduit Fitting: 25 mm (female).

FIBERGLASS ENCLOSURE—

Cover is clear polycarbonate with closed cell neoprene

gasket supplied with stainless steel screws.

CERTIFICATIONS—

CSA Certified for Class I, Division 2, Groups A, B, C

and D hazardous locations.

WEIGHT—

13 pounds (5.9 kilograms).

DIMENSIONS—

See Figure 1.

SAMPLING TUBES—

Material: Galvanized steel tubing 3/4 inch EMT, length

to be specified by customer (1, 3, 6, or 10 feet).

Return Tube: 12 inch standard length tube.

5.84

(14.8)

11.62

(29.5)

5.91

(15.0)

15.88

(40.3)

9.18

(23.3)

ALARM INDICATOR

0.31 (0.79) DIA

MOUNTING

4 PLACES

B1968

Figure 1—Dimensions of the U5006 Air Duct Smoke Detector in Inches (cm)