Testing the detector – Det-Tronics U5006 Air Duct Smoke Detector User Manual

Page 5

Advertising
background image

2.2

95-8456

5

MOUNTING SURFACE

PLUG

PLUG

DIRECTION OF AIR FLOW

DIRECTION OF AIR FLOW

MOUNTING SURFACE

RETURN TUBE

INSTALLED HERE

SAMPLING TUBE

INSTALLED HERE

SAMPLING TUBE

INSTALLED HERE

B1969

Figure 3—Tube Position and Orientation

TESTING THE DETECTOR

Disconnect alarm response devices prior to

1.

performing detector tests. Be sure to place this

equipment back into service when the testing is

completed.
Remove the clear front cover from the detector

2.

housing.
Insert plugs into the sampling and return tube outlets

3.

to prevent ducted air from carrying smoke away from

the detector sensing head.
Apply smoke directly to the detector sensing head

4.

using blown cigarette smoke, punk, or cotton wick

smoke to cause an alarm. The smoke detector tester

manufactured by Home Safeguard Industries can be

substituted if the smoke sources listed above are not

available. In this case, from a distance of three feet,

spray the smoke detector tester into the detector

sensing head in short bursts until an alarm condition

occurs.

1

2

3

4

5

NORMALLY CLOSED SUPERVISORY CONTACTS

NORMALLY OPEN ALARM CONTACTS

AUXILIARY ALARM CONTACTS

+

GROUND

YELLOW
YELLOW
VIOLET
VIOLET
BLACK
RED

TO DETECTOR

1 2 3 4 5 6

TB – 1

TB – 2

TB – 3

NOTE:

CIRCUIT SHOWN IN THE NORMAL STANDBY ENERGIZED MODE

C1192

7

10

8

9

6

Figure 4—Wiring Terminals