In normally smoky atmospheres the detector will not

go into alarm as long as the concentration is less than

the fixed sensitivity of the detector. This results in a

sensitive and positive response with the lowest potential

for unwanted alarms.

The main enclosure of the detector contains the electronic

circuitry, alarm relay, and supervision relay.

FaIlSaFE OpERaTION
To ensure reliable operation, the U5005 is equipped with

self-checking circuitry. A regulation photodiode, which

is matched to the smoke detection circuit, continuously

monitors the output intensity of the IRED and adjusts it as

necessary to compensate for an accumulation of dust or

other contaminants, or any other variation that can occur

with temperature and time. A power supervision relay in

the detector provides a trouble output signal in the event

of an input power failure.

The detector uses extensive filtering against RF and

transient interference. In addition, there is a 2 second

time delay before an alarm is generated.

The printed circuit board inside the detector is coated to

minimize the possibility of problems caused by moisture

accumulation.

DETECTOR OUTpUTS
The detector provides a set of Form A (SPST) NO

contacts for connection to the alarm output circuitry

and a set of SPST NC contacts for supervision of input

power. An auxiliary set of Form C (SPDT) NO/NC alarm

relay contacts is also provided for controlling remote

annunciation devices.

The alarm output latches on in the event of an alarm

and an LED located on the outer surface of the housing

is illuminated to provide a visual indication that an

alarm condition has occurred. The detector is reset by

momentarily interrupting input power.

SPECIFICATIONS

OPERATING VOLTAGE—

20 to 28 Vdc filtered supply, with less than 1.4 vpp at 60

to 120 Hz.

OPERATING CURRENT—

Standby:

10 milliamperes.

Alarm:

35 milliamperes.

TEMPERATURE RANGE—

Operating: –13°F to +140°F (–25°C to +60°C).

Storage:

–67°F to +185°F (–55°C to +85°C).

ALARM AND SUPERVISORy RELAy CONTACT
RATING—

1.0 ampere at 30 Vdc, SPST.

AUXILIARy ALARM RELAy CONTACT RATING—

2.0 amperes at 30 Vdc, Form C, SPDT.

jUNCTION bOX—

Body material:

Copper-free aluminum.

Conduit Fitting: 25 mm (female).

CERTIFICATIONS—

CSA:

Certified for use in Class I, Division 2,

Groups A, B, C and D hazardous

locations.

DIMENSIONS—

See Figure 2.

wEIGhT—

2 pounds (0.91 kilogram)

INSTALLATION

The U5005 is intended for surface mounting. See Figure

2. The mounting screw holes are counterbored for No.

8 flat-head screws. Electrical equipment that is used

in conjunction with the smoke detector is connected to

the detector using a terminal strip located in the junction

box that is furnished with the unit.

DETECTOR lOCaTION
The smoke detector is normally mounted on the ceiling not

less than six inches from a side wall. The exact location

of the detector must be determined by an evaluation

based on engineering judgment supplemented, if

possible, by field tests.

For additional information on detector location and

spacing, contact the National Fire Protection Association,

Batterymarch Park, Quincy, Mass. 02269, and request a

copy of NFPA Number 72, the Standard on Automatic

Fire Detectors.