MOUNTINg ThE DETECTOR

Using three No. 8 flat head screws placed through

1.

the counterbored holes in the detector flange,

secure the detector to the surface location. Secure

the junction box if necessary.
Remove the cover from the junction box and

2.

complete installation of system conduit. Feed the

external wiring through the remaining junction box

entry or M25 to 3/4 inch adapter. Use care not to

damage the wires by twisting them when installing

the junction box.
Connect the external wiring to the appropriate

3.

terminals and re-install the junction box cover. See

Figures 3, 4 and 5 for wiring details.

DETECTOR CONNECTIONS
The U5005 contains two sets of relay contacts:

One set of NO Alarm contacts close upon detection

1.

of smoke.
One set of NC Trouble contacts close when the

2.

detector is powered.