Appendix f – Det-Tronics PM-5MPX Dual Spectrum IR User Manual

Page 16

Advertising
background image

14

95-8562

4.1

APPENDIX F

p

SS-

mp

TES

T

l

A

mp

f

igur

e

f

1—

pss

-mp

t

est

lamp

LAMP

REPLACEMENT

REPLACE

XENON

LAMP

MODULE

WITH

PN

18801

(UNDER

WA

TER

KINETICS).

W

ARNING

THIS

UNIT

IS

NOT

RA

TED

FOR

USE

IN

HAZARDOUS

(CLASSIFIED)

LOCA

TIONS

.

CAUTION A

FULL

SYSTEM TEST

RESUL

TS

IN

AN

ALARM

OUTPUT

. THIS

WILL

RESUL

T

IN THE

AUT

OMA

TIC

SUPPRESSION

SYSTEM

BEING

ACTI

VA

TED

IF

IT

IS

NOT

DISABLED

PRIOR

TO

TESTING.

OPERA

TION

TURN

ON

PSS-MP

, WA

IT

15

SECONDS.

TO

CAUSE

AN

ALARM,

HOLD

PSS-MP

SO THA

T

THE

INFRARED

FIL

TER

LENS

IS

LESS THAN

1

INCH

FROM THE

FRONT

OF THE

FLAME

DETECT

OR

TO

BE TESTED.

IT

CAN T

AKE

SEVERAL

SECONDS

FOR THE

DETECT

OR

TO

ALARM.

NOTE FOR

VALID TEST

RESUL

TS, THE TEST

LAMP

AND THE

SENSOR

UNDER TEST

MUST

BE

AT

APPROXIMA

TEL

Y

THE

SAME TEMPERA

TURE.

BA

TTER

Y

REPLACEMENT

THE TEST

LAMP

REQUIRES

6

ALKALINE

C-SIZE

BA

TTERIES.

W

ARNING

CHANGE

BA

TTER

Y

IN

NON-HAZARDOUS

LOCA

TION

ONL

Y.

ON

OFF

INFRARED BEAM

INFRARED FILTER LENS

8 5/8

2 3/8

+

+

+

+

+

+

C

C

CC

C

C

Advertising