Instructions dual spectrum, Infrared flame detector pm-5mpx – Det-Tronics PM-5MPX Dual Spectrum IR User Manual

Page 3

Advertising
background image

IMPORTANT

Be sure to read and understand the entire
instruction manual before installing or operating
the Model PM-5MPX Detector. Only qualified
personnel should install, maintain or operate the
flame detection system.

CAuTION

If this equipment is used in a manner not specified
in this manual, safety protection may be impaired.

CAuTION

The wiring procedures in this manual are intended
to ensure proper functioning of the device under
normal conditions. However, because of the many
variations in wiring codes and regulations, total
compliance to these ordinances cannot be
guaranteed. Be certain that all wiring complies
with the NEC as well as all local ordinances. If in
doubt, consult the authority having jurisdiction
before wiring the system.

The Dual Spectrum

®

PM-5MPX is a FM Approved

infrared flame detector that provides reliable flame

detection in semiconductor fabrication facilities and other

manufacturing environments. It provides fast protection

against fires, has a maximum 110° field-of-view, and is

approved for use in hazardous (classified) locations as

described below. The detector response to explosive

fires is as fast as 25 milliseconds.

The PM-5MPX (P/N 421132) is encapsulated and

enclosed in an extremely compact molded polypropylene

housing approximately 3.1 x 3.1 x 1.7 inches in size. (See

Figure 1.) They are intended for mounting in locations

where space is at a premium. The IP67 polypropylene

housing is resistant to attack by a broad range of

chemicals. The housing has four holes in the mounting

flange that allow it to be attached to a bracket or other flat

surface. Electrical connections are made via an integral

multiconductor cable.

FM Approved for:

1) performance of the flame detector per FM 3260: 2000,

2) compliance with National Fire Protection Association

(NFPA) Standard 72 of the detectors and the

installation described in this document,

3) the suitability for use in protected semiconductor

fabrication areas, as described in the FM Loss

Prevention Data Sheets 7-7/17-12, and

4) the suitability of the installation for use in hazardous

(classified) locations.

NOTE

These detectors are specifically tuned and tested
to respond to fires as described in this manual. The
detector response to other fuel sources not
described in this manual may vary. Please contact
Detector Electronics Corporation for further
information.

APPLICATIONS

The PM-5MPX is intended for fast detection of

hydrocarbon fueled fires in harsh chemical environments.

The detector is ideal for semiconductor wet benches

and is suitable for clean-rooms, gas cabinets, and other

indoor applications.

4 .1

©Detector Electronics Corporation 2013

rev: 8/13

95-8562

INSTRUCTIONS

Dual spectrum

®

infrared flame Detector

pm-5mpX

FM

APPROVED

®

Advertising