SYMPTOM:

RATIO voltage is negative or 4-20 mA output is below 4 mA.

POSSIBLE CAUSE:

The ZERO adjustment potentiometer located on the front panel is not set properly.

CHECK:

Setting of ZERO adjustment potentiometer on front panel.

REMEDIAL ACTION:

Adjust ZERO potentiometer until RATIO is 1.0 ±0.5 VDC (See Output Zero OPERATION/
PERFORMANCE CHECK procedure).

POSSIBLE CAUSE:

Instrument malfunction.

CHECK:

NUMERATOR and DENOMINATOR voltage when a bare flashlight bulb or bare 60 watt light
bulb is held in front of the receiver window.

REMEDIAL ACTION:

Replace printed circuit boards one at a time and repeat

CHECK. Contact factory if fault

cannot be located.

SYMPTOM:

RATIO voltage is steady and does not appear to be responding to oil within field-of-
view.

POSSIBLE CAUSE:

Malfunction of signal processing circuitry.

CHECK:

RATIO voltage when a small amount of oil is introduced within the instrument’s field of view.
The RATIO voltage should increase above +2.0 VDC.

REMEDIAL ACTION:

Substitute spare boards and assemblies until defective part is located and RATIO responds
properly to oil. Defective part can be returned to factory for analysis and repair.

SYMPTOM:

Oil Alarm does not activate when oil is present in instrument’s field-of-view, or Oil
Alarm activates too frequently.

POSSIBLE CAUSE:

Improper Oil Alarm threshold setting.

CHECK:

Voltage at OIL ALARM SETPOINT test jack (grey) relative to SIGNAL GROUND (green).

REMEDIAL ACTION:

Adjust setpoint if required. See Oil Alarm Threshold Adjustment procedure.

POSSIBLE CAUSE:

Malfunction of Oil Alarm circuitry.

CHECK:

RATIO voltage relative to voltage on OIL ALARM SETPOINT jack. If RATIO voltage exceeds
alarm setpoint, and alarm does not activate, a malfunction of alarm circuitry exists.

REMEDIAL ACTION:

Replace Rear Panel p.c. board and/or Oil Alarm relay on Connector/Relay p.c. board.

SYMPTOM:

Signal strength of NUMERATOR and DENOMINATOR decreases when water becomes
calm.

POSSIBLE CAUSE:

Transmitter and receiver not properly aligned.

REMEDIAL ACTION:

Repeat Alignment procedure.

SYMPTOM:

RATIO output is negative or very positive and does not respond to oil on the water.

POSSIBLE CAUSE:

Transmitter and receiver not properly aligned.

CHECK:

NUMERATOR voltage.

REMEDIAL ACTION:

If NUMERATOR voltage is less than +0.25 VDC, repeat Alignment procedure.

17