Beckett AQUASMART 7600 User Manual

Page 2

Advertising
background image

Form No. 61749 R01, Printed in the USA

1

1/09

Table 2 - Functional Replacement (Advanced Wiring Needed)

Note: Available operating limit and/or differential ranges may not be equivalent. Compare settings to the AquaSmart ranges before replacing.

Honeywell

Beckett Replacement

Notes

L4006A (All)
L4006G 1022
L4006H 1004
L4008A (All)
L4080B,D

7600A or 7600B

(Based on System

Voltage Requirements)

Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.
7600 will require an additional wire (L2) for operation. Short TW-TR terminals. C1, C2, ZC, and ZR are unused.
Set low limit on 7600 to OFF.
To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must be added to switch the
millivolt circuit.

L4006E (All)
L4008E (All)
L4080F,G

Requires the addition of a manual-reset high limit.
Make sure 7600 outputs do not exceed 7.4A @ 120VAC.
7600 outputs are not rated for 240 VAC.
7600 will require an additional wire (L2) for operation. Short TW-TR terminals. C1, C2, ZC, and ZR are unused.
Set low limit on 7600 to OFF.
To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must be added to switch the
millivolt circuit.

L6006A (All)
L6006C 1018
L6008A 1192
L6008A 1242

Not a suitable replacement if SPDT switch action is required; only break-on-rise available on 7600.
To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must be added to switch the
millivolt circuit.
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.
7600 will require an additional wire (L2) for operation. Short TW-TR terminals. C1, C2, ZC, and ZR are unused.
Set low limit on 7600 to OFF.

L8124B 1039
L8148J 1009

To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must be added to switch the
millivolt circuit. 7600 outputs are not rated for 240 VAC.

L7148F (All)
L8148E (All)

7600B

Must confi rm that 7600 VA rating is adequate to meet VA requirements of system.
Make sure 7600 B1 output does not exceed 1.25A @ 24VAC (30 VA).
7600 outputs are not rated for 240 VAC. B2, TW and TR terminals replace TV, T and Z, respectively.
If damper is used, consult damper manufacturer’s wiring instructions for using damper without damper plug.

L4081A,B
L6081A,C

7600A or 7600B

(Based on System

Voltage Requirements)

Remove switching relay, if used, from the system when replacing the L4081 or L6081
Make sure 7600 outputs do not exceed 7.4A@120VAC. 7600 outputs are not rated for 240 VAC.

Carlin

Beckett Replacement

Notes

90200A

7600A or 7600B

(Based on System

Voltage Requirements)

Make sure 7600 outputs do not exceed 7.4A. Set low limit on 7600 to OFF.

90000 (All)
90200E
90200EL
90300B

Requires the addition of a manual-reset high limit. Make sure 7600 outputs do not exceed 7.4A.
Set low limit on 7600 to OFF.

90200D

Not a suitable replacement if SPDT switch action is required; only break-on-rise available on 7600. Make sure 7600
outputs do not exceed 7.4A. Set low limit on 7600 to OFF.

White Rodgers

Beckett Replacement

Notes

11B06-1
11D18-1
11B18-101
11B30-104
11B02-1
1145-33
11B06-46
11B95-31
11B18-153

7600A or 7600B

(Based on System

Voltage Requirements)

Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC. 7600 will require an
additional wire (L2) for operation. Short TW-TR terminals. C1, C2, ZC, and ZR are unused.
Set low limit on 7600 to OFF.

11D82-1
11D31-1
1131-102
1127-2
11A79-2
1127-9

Not a suitable replacement if SPDT switch action is required; only break-on-rise available on 7600. 7600 outputs are not
rated for 240 VAC.
7600 will require an additional wire (L2) for operation. Short TW-TR terminals. C1, C2, ZC, and ZR are unused.
Set low limit on 7600 to OFF.

11B27-9

Requires the addition of a manual-reset high limit.
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC. 7600 will require an
additional wire (L2) for operation. Short TW-TR terminals. C1, C2, ZC, and ZR are unused.
Set low limit on 7600 to OFF.

8J48A-209

To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must be added to switch the
millivolt circuit.

Advertising