OPERATING INSTRUCTIONS

One Monitor Control
This operator control panel has one set of switches and pilot lights to operate one monitor.

Monitor Functions – UP, DOWN, LEFT, & RIGHT are operated with spring return joysticks. This is

accomplished by using the proper selector/pushbutton joystick to move the monitor the direction

desired. When joystick is released, it will return to original (off) position, and monitor movement

will stop.

Monitor Manual Control

Vertical Manual Override – Push hand wheel inward to engage override. While holding the

hand wheel in, rotating it clockwise will raise the nozzle, and rotating it counter-clockwise will

lower the nozzle.

Horizontal Manual Override – Push hand wheel inward to engage override. While holding hand

wheel in, rotating it clockwise will move the monitor right, and rotating it counter-clockwise will

move the monitor left.

When monitor operation is completed, move vertical movement to full down position to allow water to

drain from nozzle. When water is drained from nozzle, move monitor to park position.

MAINTENANCE

Monthly Inspection & Maintenance

Cycle all monitor functions (LEFT, RIGHT, UP, DOWN) to insure the complete system is fully

functional.

Six-Month Inspection & Maintenance

Grease monitor ball races through grease fittings located at each swivel joint. Recommended

grease for Industrial Spit-Fire® monitors is MOBILITH SHC – 100, High Performance Synthetic

Grease. Temperature range: -40°F (-26°C) to 400°F (250°C) or equal. Greasing procedures are

as follows:

o

Apply approx. 5-7 pumps of grease in the lower grease fitting, and 2-3 pumps in the

upper grease fitting

Check motor control cables for water and connectors for damage.

Check motor cables for binding through full movement of monitor.

Check all painted surfaces for chips or scratches, and repaint as required.

Visually check all electrical equipment.

Warning:

Do not attempt to disconnect or work on any electrical equipment in this

system unless power is removed or the area is known to be non-hazardous.