Warning – Elkhart Brass SPIT-FIRE 8394053 Monitor User Manual
Page 11
11
VI MAINTENANCE
Monthly Inspection & Maintenance
1. Check all terminal blocks and connections for being properly taut to 4.5 – 7.1 in-lbs (0.508 – 0.802
Nm).
2. Check all contact blocks and operators for functionality. If there are loose connections tighten them. If
a contact block is not functioning properly, replace it.
3. Check all light bulbs on outside of the panel. If any are burnt out, replace the bulb.
4. Check for proper operation of system overall. Please refer to the Troubleshooting section if you are
experiencing problems.
VII TROUBLESHOOTING
A. If Panel will not power up:
1. Check the incoming supply power, and if it’s the proper power requirement for the system.
2. Check fuses in panel to affirm they are good. If fuses are blown, replace them with same or
equivalent fuse.
a. Check for causes in the interconnect wiring and connections.
b. Verify that the OCP/NCP is not trying to activate the monitor motor functions.
c. If nothing is found consult with your Elkhart Brass representative.
3. Check panel power switch to make sure it is in the “Power On” position.
B. Pushbutton/Joystick not working properly:
1. Check screws that tighten contact block to actuator, they may need an adjustment.
2. Check screw terminations on contact block for being tight.
3. Check that the contact block itself is good, if not, replace it.
C. If Pilot Light is not on when panel has power:
1. Check the light bulb, if it is burnt out, replace it.
D. Function not working correctly:
1. Check to see if there is a loose connection, at the terminal blocks or contact blocks. Make sure all
screw terminations are properly tightened to 4.5 – 7.1 in-lbs (0.508-0.802 Nm).
2. Check relay for actuation. If bad, replace relay with new working relay.
E. Water or Foam valve will open but will not close when operated.
1. Verify that jumpers between terminals (10 and 14) or (15 and 19) are removed.
Please refer to our website at
www.elkhartbrass.com
for any further information. Any problems that
cannot be fixed/solved should be taken to your Elkhart Brass Representative.
WARNING:
Do not attempt to disconnect or work on any electrical equipment in this
system unless power is removed or the area is known to be non-hazardous.