Warning – Elkhart Brass SPIT-FIRE 8394053 Monitor User Manual

Page 4

Advertising
background image

4

I OVERVIEW

This panel is a universal panel that depending on how it is configured or used can be set-up in multiple
combinations to achieve the desired system configuration. Panel set-up/programming procedure is in the OCP
manual. It has a selector switch for Power On and will also have pushbuttons for Park, Oscillate On and Off,
water valve Open and Close, and foam valve Open and Close. It includes a two position joystick to do Nozzle
Fog to Straight Stream, and a four position joystick to move the monitor UP/DOWN/RIGHT/LEFT. Only one
movement can be achieved at a time. Lights include Power On, Oscillation, water valve opened, foam valve
opened, and park. This box will operate the monitor(s) and can represent a stand alone system.

OCP as Local Operator Control Panel (LOCP):

This box will be hardwired directly to one or more MMCP’s.

OCP as Remote Operator Control Panel (ROCP):

This panel is an Operator Control Panel with the exception that it is not connected directly to the MMCP. It
will communicate to the LOCP through a network connection of either fiber optic or an Ethernet cable.
Additional panels can be added to control specific monitors if desired through this same method. Joysticks
and controls can operate any monitor on the system network.

OCP as Network Control Panel (NCP)

This box is different from the other two boxes in that it will have no manual pushbuttons, joysticks, or
monitor function lights. It only contains the Power On/Off switch and the Power On indicator light much
like that of the MMCP. This means that the monitors in the system are controlled from another external
device.

Electrically Operated Master/Local/Network Control Panel (OCP) Features:

Construction – Stainless Steel enclosure rated for Hazardous Location (Class 1, Division 2)
Compliance – (NFPA 70) NEC: 2008, Article 501 – Class I, Groups “B, C, & D,” Division 2 & Article

505 – Class I, Zone 2, T3C requirements; UL Labeled.

Control Power – On/Off 2-Position selector switch.

Pilot Lights – Shows panel power On; water and foam valves Opened, Park, and Oscillation function

On.

Internal Power – 24 VDC Power Supply for controls.

Controls – NEMA 4 (IP-66) controls. Joystick controls for monitor and nozzle movement (UP, DOWN,

LEFT, RIGHT, STRAIGHT STREAM, and FOG) and pushbutton controls for Park, Oscillation On/Off,
Water Valve OPEN/CLOSE, and Foam Valve OPEN/CLOSE.

Conduit Knockouts and Hubs – Supplied by customer.

WARNING:

Do not take cover off the Nozzle Motors. If cover is/has been removed, the

warranty is void and the service life of the motor is significantly reduced.






Advertising