Warning – Elkhart Brass SPIT-FIRE 8394053 Monitor User Manual

Page 9

Advertising
background image

9

VI TROUBLESHOOTING

A. If Panel will not power up:

1. Check the incoming supply power, and if it’s the proper power requirement for the system.
2. Check to make sure the transformer is wired correctly.
3. Check fuses in panel to confirm they are good. If fuses are blown, replace them with same or

equivalent fuse.

a. Check for causes in the interconnect wiring and connections.
b. Verify that the OCP is not trying to activate the monitor motor functions
c. If nothing is found consult with your Elkhart Brass representative.

4. Check panel power switch to make sure it is in the “Power On” position.
5. Check power supply to confirm there is 120 VAC running to it.

B. If Pilot Light is not on when panel has power:

1. Check the light bulb, and replace if it is burnt out.

C. Function not working correctly:

1. Check to see if there is a loose connection at the terminal blocks or contact blocks. Make sure all

screw terminations are properly tightened to 4.5 – 7.1 in-lbs (0.508 – 0.802 Nm)

2. Check relay for actuation. If bad, replace relay with new working relay.

Any problems that cannot be fixed/solved with this troubleshooting guide should be taken to your
Elkhart Brass Representative to get further information.

WARNING:

Do not attempt to disconnect or work on any electrical equipment in this

system unless power is removed or the area is known to be non-hazardous.