Elkhart Brass X-Stream SM1000BE – SM2000BE HL/HLGM User Manual

Page 6

Advertising
background image

6

III INSTALLATION INSTRUCTIONS

Installation Steps

1. Insure the gasket is present in the nozzle before installing onto Stream Shaper (Model# 284-B).

2. Position nozzle so the motor is located on the top of the nozzle. You may position the motor on the

left side of the nozzle as well; however, we recommend the top position for optimal clearance.

3. Tighten the Stream Shaper to monitor using a spanner wrench. Then tighten the nozzle swivel base

to the Stream Shaper.

4. Install cable plug to the receptacle on the nozzle motor aligning locator key in plug with key in

receptacle. Screw swivel down tight on male thread of receptacle.

5. Install corrugated black safety boot on cable connector so split lines up with cable. Install clamp

around top of boot and connector swivel. Tighten clamp around swivel and boot.


IV SPECIFICATIONS

General Specs

 Input Power

120 VAC (50/60Hz.) 1 Phase

 Electrical

Load 0.30

AMPS

 Nozzle Dimensions

Ø6 7/8” X 9 5/16” L (SM1000BE-HL & SM1250BE-HL)

 Nozzle Dimensions

Ø7 15/16” X 9 7/8” L (SM2000BE-HL)

 Nozzle Weight

Approx. 32 lbs

 Operating Temperature Range

-40

o

C to +85

o

C

ATEX Product Marking

II 3 G c T3

Ex nA IIC T3


V OPERATING INSTRUCTIONS

Nozzle is normally electrically actuated through Monitor Control System. It will free wheel at both ends of
stroke (fog and straight stream). Please note that the nozzle does not have a shut-off function.

When monitor is not in use, return it to its designated park position. We recommend storing in full fog facing
downward to allow nozzle to drain. However, some operating requirements may override this.

Manual Override Operation

1. Push knob in and hold to engage manual override.

2. Turn knob clockwise to move nozzle tip into fog position, and counter-clockwise to move nozzle tip

into straight stream position.