Close position limit setting (Position Seating)

- Enter setup mode: move switch SW3 to the ON position
- Move the actuator to the closed position using the handwheel
- Rotate switch SW4 to position 0
- Rotate switch SW6 to position 0
- Confirm by pushing ENTER pushbutton SW5
- When pushing SW5, the red LED will blink once to confirm that the setting is accepted
- Exit setup mode (move switch SW3 to position 1) or proceed to the next step:



Open position limit setting (Position Seating)

- Enter setup mode: move switch SW3 to the ON position
- Move the actuator to the open position using the handwheel
- Rotate switch SW4 to position 1
- Rotate switch SW6 to position 0
- Confirm by pushing ENTER pushbutton SW5
- When pushing SW5, the red LED will blink once to confirm that the setting is accepted
- Exit setup mode (move switch SW3 to position 1) or proceed to the next step:



Close position limit setting (Torque Seating)

Important: Refer to Actuator Default Settings above.


To modify the default setting, proceed as follows:

- Enter setup mode: move switch SW3 to the ON position
- Rotate switch SW4 to position 2
- Rotate switch SW6 to position 0
- Confirm by pushing ENTER pushbutton SW5
- When pushing SW5, the red LED will blink once to confirm that the setting is accepted
- Electrically operate the actuator in the close direction until the actuator stops
- Exit setup mode (move switch SW3 to position 1) or proceed to the next step:



Open position limit setting (Torque Seating)

Important: Refer to Actuator Default Settings above.


To modify the default setting, proceed as follows:

- Enter setup mode: move switch SW3 to the ON position
- Rotate switch SW4 to position 3
- Rotate switch SW6 to position 0
- Confirm by pushing ENTER pushbutton SW5
- When pushing SW5, the red LED will blink once to confirm that the setting is accepted