Elkhart Brass ELKHART PRESSURE-MATIC VALVES User Manual

Page 2

Advertising
background image

2

Valve Model

Bonnet Type

Max. Flow (gpm)

Max. Pressure (PSI)

A

500

400

B

500

400

C

500

400

CD

500

400

D

500

360

DE

500

330

E

500

290

EF

500

250

UR-20 & UR-25

2-1/2"

F

500

220

A

400

400

B

400

400

C

400

400

CD

400

400

D

400

360

DE

400

330

E

400

290

EF

400

250

UR-20S

2-1/2”

F

400

220

W

200

300*

X

200

300*

Y

200

300*

YZ

200

300**

Z

200

300***

ZA

200

280

ZB

200

250

ZZ

200

220

UR-20 & UR-25

1-1/2"

ZZA

200

190

* ULC rated to 400 PSI

** ULC rated to 394 PSI

*** ULC rated to 316 PSI

These valves are also listed as a checking device, which eliminates the need for a separate check valve. When

sprinklers on a given floor are fed from dual risers, the Pressure-Matic® valve acts as a check valve to prevent

loss of sprinkler water supply in the event of damage to one riser.

Supervisory Switch Mounting Brackets

Brackets are available for the attachment of the following listed supervisory switches to the Pressure-Matic®

valves.

Switch Mfr. & Model No.

Bracket No.

OSYS-B

80738001

PCVS

80574001

PIVS-B

80736001(

for sprinkler application

)

" "

80763001(

hose valve application

)

PIVSU-A1

80823001

Potter Electric

PIVSU-A2

80823001

PIBV2

80574001

System Sensor

OSY2

80574001

Advertising