3.4.5
Isolated AC Supplies (with an Isolation Transformer) Wiring
Diagrams
Figure 6: Single-Phase Isolated Source Connection
Caution:
•
When using a single-phase AC source, terminals AC2 and AC3 must be paired
together in a shared connection.
•
When using an isolation transformer, PR and PE must be connected together on the
Tambourine 20 side.
Figure 7: Three-Phase Isolated Source Connection
Caution
:
When using an isolation transformer, PR and PE must be connected together
on the Tambourine 20 side.