Panel System shall be the Englert Series 4000, 1-1/2” x 12” or 14” wide, Flat Panels. Flush wall soffiit is available with
ribs. All fasteners shall be concealed, and panels shall give a flush appearance. The soffit panels shall have the
same finish as the roofing system. The panels shall have baked on finish as specified in Section 2.05 hereunder, in
Manufacturer’s standard colors. Manufacturer shall offer at least a minimum of 23 standard colors to choose from.

B.

Substrate:

?

24 Gauge baked on finish over Galvalume ASTM A-792-83, AZ50, 50 KSI yield point, 52 KSI tensile strength.

?

* 22 Gauge baked on finish over Galvalume per ASTM A-792-83, AZ50, 50 KSI yield point, 52 KSI tensile

strength.

?

* .032” or .040” Aluminum Alloy 3105-H14 approved equal.


NOTE TO SPECIFIER: *22 gauge steel, and .032” and .040” aluminum are available subject to minimum
order requirements. Call Englert for d etails.

C.

Performance:

1. Panel shall display a flame spread classification of a (Class 1) when tested in accordance with ASTM E-84-87.

2.03 ENGLERT FLUSH WALL ALLOWABLE PANEL SPAN

(Feet Inches)

Wind Load (Lbs/Sq. Ft)

Panel

Gauge

Panel

Width

No. Of

Equal Spans

20

25

30

35

40

45

50

55

24 Gauge

14”

1

6’ - 5”

5’ - 11”

5’ - 7”

5’ - 4”

5’ - 1”

4’ - 11”

4’ - 9”

4’ - 7”

Steel

3

8’ - 1”

7’ - 6”

7’ - 1”

6’ - 9”

6’ - 2”

6’ - 2”

6’ 0”

5’ - 9”

22 Gauge

14”

1

6’ - 11”

6’ - 6”

6’ - 1”

5’ - 9”

5’ - 6”

5’ - 4”

5’ - 1”

4’ - 11”

Steel

3

8’ - 9”

8’ - 2”

7’ - 8”

7’ - 3”

6’ - 11”

6’ - 8”

6’ - 5”

6’ - 3”

24 Gauge

12”

1

6’ - 9”

6’ - 3”

5’ - 11”

5’ - 7”

5’ - 4”

5’ - 2”

5’ - 0”

4’ - 10”

Steel

3

8’ - 6”

7’ - 11”

7’ - 5”

7’ - 1”

6’ - 9”

6’ - 6”

6’ - 3”

6’ - 1”

22 Gauge

12”

1

7’ - 4”

6’ - 9”

6’ - 5”

6’ - 1”

5’ - 10”

5’ - 7”

5’ - 4”

5’ - 3”

Steel

3

9’ - 3”

8’ -7”

8’ - 1”

7’ - 8”

7’ - 4”

7’ - 1”

6’ - 9”

6’ - 7”

2.04 FABRICATION

A.

Panel Construction: Panels shall be uniformly dimensioned, rollformed to exact lengths to avoid trimming. The panel
system shall be anchored as recommended by the Manufacturer. All fasteners shall be concealed. Panels shall be
continuous from ridge to eaves with no end laps. There shall be no face penetration of panels, except as approved by
the architect for securing panels to facilitate directional expansion/contraction.

B.

Flashing and Trim: All exposed standard or special flashing/trim and such other brakeformed in the same gauge, color,
and finish to match roofing panels, furnished with protective strippable film to be removed upon installation.

C.

Accessories such as closures, fasteners, etc., shall be as recommended by the Manufacturer.