Operating Instructions Safety Switch CES-AP-C.2-CH

16

System status table

Operating mode

Actuator/

door position

Safety outputs

OA and OB

LED indicator

output

State

ST

ATE (gr

een)

DIA (r

ed)

Normal operation

closed

on

Normal operation, door closed

closed

on

flashes 

quickly

2 Hz

Normal operation, door closed, actuator in the boundary area 

¨

 Re-adjust door

open

off

1 x

Normal operation, door open

Fault display

closed

off

3 x

Defective actuator (e.g. fault in code or code not readable)

X

off

4 x

Output error  

(e.g. short circuits, loss of switching ability)

X

off

5 x

Internal fault (e.g. component faulty, data error)

Key to symbols

LED not illuminated

LED illuminated

10 Hz (8 s)

LED flashes for 8 seconds at 10 Hz

3 x

LED flashes three times, and this is then repeated

X

Any state

After  the  cause  has  been  remedied,  faults  can  generally  be  reset  by  opening 

and closing the door. If the fault is still displayed afterward, briefly interrupt the 

power supply. Please contact the manufacturer if the fault could not be reset after 

restarting.

Important:

If you do not find the displayed device status in the System status table, this indi-
cates an internal device fault. In this case, you should contact the manufacturer.