3 Troubleshooting

3.1 LED DIA illuminated + LED STATE not illuminated (AR and AP

modes)

Fault symptom:

The MGB displays the fault state “internal fault”.

Possible fault causes:

 Data

error

 Locking

arm

blocked

 Internal component fault

Remedy:

1. Check whether the locking arm is blocked (possibly by the bolt of the handle module).
2. Switch the voltage off at all devices

or
press the reset button (if present) that controls ALL integrated reset inputs in the series connection

3. Close the door(s).
4. Switch the voltage on again

or
release the reset button

5. Wait until the STATE LED flashes with the code “LONG ON, SHORT OFF”.

 The MGBs are now ready for operation again

6. If the fault persists, please send in the device for inspection

3.2 LED DIA illuminated + LED STATE flashes 1 time (AR and AP modes)

Fault symptom:

The MGB displays the fault state “fault during teach-in/configuration or invalid DIP switch position”.

Possible fault causes:

 Invalid DIP switch position

1. Malfunction due to incorrect configuration of the DIP switch

Remedy:

1. Check of the DIP switch setting. Configuration must be repeated if the setting is incorrect. Follow the

instructions “Changing device configuration” in the system manual (section 10.5).