Ảả ạ, 7setting the control – Hydrolevel 3250-Plus User Manual

Page 7

Advertising
background image

Zone/Indirect Switch

NOTE: Settings can be checked using the

TEST/SETTINGS Button. See page 11 for details.

Setting the High Limit

The high limit is factory set at 190°F. To adjust, turn the HI

TEMP Dial

until the desired setting is displayed. (Setting

range: 100°-220°F)

Setting the Low Limit

The low limit is designed to maintain temperature in boilers

equipped with tankless coils used for domestic hot water.

The low limit is factory set to OFF. Prior to adjusting, remove

the jumper (not equipped on all units)

. Then turn the LO

TEMP Dial

clockwise until the desired temperature is dis-

played. For proper operation, the low temperature limit set-

ting should be at least 10° below the high limit setting.

NOTE: For cold start operation, the low limit must be turned

OFF. IMPORTANT: If low limit temperature cannot be set

above 140°F, remove jumper

. (Setting range: OFF or

110°-200°F).

Setting the Economy Feature

The Economy Feature is factory set for a 1 zone heating sys-

tem. To adjust, turn the ECONOMY Dial

until the number

displayed equals the number of heating zones. Do not

include indirect water heaters in the number of heating

zones. The Economy Feature conserves fuel by reducing

boiler temperature (see “How Thermal Targeting Works” on

page 8). If the heating system is unable to supply needed

heat to the house, the ECONOMY Dial should be turned to a

lower setting (example: In a three zone house, turn the dial to

2 or 1). Conversely, if the boiler provides adequate heat,

added fuel savings can be achieved by selecting a higher set-

ting (example: 4 or 5). If the heating and indirect water heater

signals were not separated when wiring the control, the

Economy Feature should be turned OFF to ensure the boiler

supplies adequate temperature to heat the indirect tank.

Setting the Zone/Indirect Switch

See WIRING on page 4-6.

7

SETTING THE CONTROL

Dynamic

Display

Water Temperature

and Real Time

Verification of

Setting Adjustments.

Low Temperature

Limit Setting

(OFF or 110°-200°F)

Factory OFF

High Temperature

Limit Setting

(100°-220°F)

Factory 190°F

Spade Connectors

for OS-100 Outdoor

Sensor Kit

Diagnostic LEDs

Economy Dial

(OFF or LO, 1, 2, 3,

4, 5, HI)

Differentials

are automatic

and will vary

based on

control settings

and boiler tem-

perature.

SETTING

Disables economy function. Will allow boiler to fire until hi-
limit temp is reached and re-fire with a 10° subtractive
differential.

Provides lowest level of fuel savings. Use this setting only if
the house does not stay warm at higher settings.

Recommended setting for single zone systems

Recommended setting for Two zone systems

Recommended setting for Three zone systems

Recommended setting for Four zone systems

Recommended setting for Five zone systems

Provides highest level of fuel savings

Indicator Light

(announces heat call)

Jumper

Test/Settings Button

HydroStat 3250-Plus Instructions: HydroStat Instructions.8pg 11/14/13 3:43 PM Page 7