Power supply input connections – Johnson Systems DMX 6-PORT MERGER User Manual

Page 9

Advertising
background image

WWW.JOHNSONSYSTEMS.COM

9

Models: DMX-6PM-XLR, DMX-6PM-TB, DMX-6PM-RJ45

For portable or permanent installation applications. Set on a flat surface in

just about any indoor location. Rubber feet on the bottom of the enclosure

help keep the enclosure in place.

Models: DMX-6PM-XLR-RM, DMX-6PM-TB-RM, DMX-6PM-RJ45-RM

For 19

"

rack mount applications. Two (2) 19" rack mounting brackets are

provided. To install the brackets, use a #2 Philips screwdriver to remove the

four (4) (two (2) per side) mounting screws on the front-left side and front-

right side, and fasten the brackets in place using the same mounting screws.

Install the unit in a 19" rack using standard rack mounting hardware (not

included).

Power Supply Input Connections

Models: DMX-6PIM, DMX-6PIM-FM

AC Power Supply Input: 100-240VAC, 1P3W, 20A (MAX), 50/60Hz.
With the lid removed, the AC power supply input termination area is located

at the top of the enclosure. A break-away style terminal block is provided for

the AC power supply input connections. Two (2) 1.109" knockouts (suitable

for 0.75" conduit) are located on the top of the enclosure. The top-left

knockout location is recommended for the AC wire (conduit) entry. Unplug

the terminal block to terminate the three (3) wires. Use a 1/8" flathead

screwdriver to torque the power terminals to the specification provided below.

Once the wire termination is complete, plug the terminal block back in and

ensure it is fully seated. Verify all wiring terminations and secure the lid

before powering up.

• AC power supply connections: HOT (LINE), NEU (NEUTRAL),

GND (GROUND)

• Use wire size #18 to #12 AWG (stranded or solid core) copper wire only,

rated for 167°F (75°C) minimum.

• Strip insulation length to 0.25" (6.4mm).

• Torque power terminals (HOT, NEU, GND) to 4.5 IN-LBS (0.5 NM).

WARNING: AC power supply input requires an external disconnect

(circuit breaker)!

WARNING: AC wiring termination must be completed by qualified

personnel only!

WARNING: For connection use copper wire only, rated for

167°F (75°C) minimum.

WARNING: Ensure all AC power supply connections are tightened to

the torque specification provided, before turning on the AC

power supply!

WARNING: Ensure the enclosure lid is secure before turning on

the AC power supply!