Actvar control, Actvar serial, Actvar eprog – JULABO SC 10000w Professional Series Recirculating Coolers User Manual

Page 44

Advertising
background image

Menu functions

44

9.3.5.

ACTVAR - actuating variable

XXXXX

ACTVAR
CONTROL

Factory setting:
CONTROL

XXXXX

ACTVAR
SERIAL

XXXXX

ACTVAR
EPROG

The variable (ACTuating VARiable) corresponds to the extent to which
the heater or cooling machine of the recirculating cooler is controlled.
Heat or cold is applied to the bath according to this variable. If this
happens with the control electronics of the recirculating cooler, called
> CONTROL < in this particular case, the bath temperature is exactly
heated and maintained constant at the adjusted setpoint.

Programming of variables for the parameters > SERIAL < or >
EPROG < is only accepted, if the unit is in Start mode.

1.

Press the

button until the submenu > ACTVAR < is displayed.

2.

Select the parameter with the keys

(CONTROL / SERIAL / EPROG )

3.

Press enter

to store the selected parameter

Continue: Press

/

or

Possible parameters:

CONTROL

– The internal control electronics of the recirculating cooler

controls the heater and cooling machine. Self-tuning is possible.

SERIAL

– The heater or cooling machine receives the control signal via

the serial interface. Self-tuning is not possible.

EPROG -

The heater or cooling machine receives the control signal via

the E-Prog input. Self-tuning is not possible.

Important:

Under >MENU ANALOG< set the input variable to
>EPROG x / ACTVAR< (see page 61).

XXXXX

EPROG U

ACTVAR

 Example: EPROG U / ACTVAR

Note:

The E-Prog input can only be used either under menu item
> SETP < (page 41) or under menu item > ACTVAR <.



Advertising