3 connection diagram, Connection diagram, 3 electrical connection – JUMO 709061 TYA 201 - Single-Phase Power Controller Operating Manual User Manual

Page 34: Power sec- tion, Connection for screw terminal x2_1, Connection for screw terminal x2_2, 5k w

Advertising
background image

3 Electrical connection

32

2012-12-01/00561071 [SCR Power Controller TYA201]

3.3 Connection diagram

Control section

Master-slave
connection

Connection for

Screw terminals

Connection side Device
side

Voltage supply for control electronics
(Corresponds to the max. load voltage
of the ordered device type)

L1
N/L2
V

Protective earth

PE

Load connection in the

power sec-

tion

U1
U2

Fan X14

20, 21 (only for load current 250 A)

V

V

PE

PE

U2

U1

N/L2

L1

Connection for

Screw terminal X2_1

Connection side Device side

Current setpoint input

1
2

Voltage setpoint input (surge proof
up to max. DC +32 V)

3 (GND)
4

Output DC 10 V fixed voltage
(max. +10 V, 2 mA)

5

Ground potential

6 (GND)

2

1

+

I

x

4

3

+

U

x

E

S

A

3

4

5

5k

W

External manual
adjustment with

Connection for

Screw terminal X2_2

Connection side Device side

Firing-pulse inhibit
Surge proof up to max. DC 32 V
OFF logical "0" = 0 to +0.8 V
ON logical "1" = +2 to 3.3 V

8
7 (GND)

Binary input1
Surge proof up to max. DC 32 V
OFF logical "0" = 0 to +0.8 V
ON logical "1" = +2 to 3.3 V

9
11 (GND)

Binary input2
Surge proof up to max. DC 32 V
OFF logical "0" = 0 to +0.8 V
ON logical "1" = +2 to 3.3 V

10
11 (GND)

GND

7, 11

Ground potential

Analog output
Various internal controller variables can
be output as a standard signal 0(4) to
20 mA, 0(2) to 10 V, 0(1) to 5 V.

v Chapter 10.4 "Analog output (actu-

al value output)"

12

7

8

3,3V

10k

W

11

9

3,3V

10k

W

11

10

3,3V

10k

W

12

11

+

Connection

RJ 45 socket X8

For master-slave operation in
three-phase current economy circuit

1:1 patch cable