Kees IFG (INDIRECT FIRED GAS) MAKE-UP AIR UNITS - Duct Furnace Installation & Maintenance Manual User Manual

Page 23

Advertising
background image

– 23 –

Chart 6 - Trouble Shooting continued

SYMPTOMS

E. Flame lifting from burner ports.

F. Flame pops back.

G. Noisy flame.

H. Yellow tip flame (some yellow

tipping on propane gas is per-
missible.

POSSIBLE CAUSES

8. Defective transformer.

9. Loose wiring.

10. Defective ignition control.

1. Pressure regulator set too

high.

2. Defective regulator.

3. Burner orifice too large.

1. Excessive primary air.

1. Too much primary air.

2. Noisy pilot.

3. Irregular orifice causing whistle

or resonance.

4. Excessive gas input.

a. Pressure regulator set too
high.
b. Defective regulator.

c. Burner orifice too large.

1. Insufficient primary air.

2. Clogged main burner ports.
3. Misaligned orifices.
4. Air shutter linted.

5. Insufficient combustion air.

6. Clogged draft hood/flue collec-

tor.

CORRECTIVE ACTION

8. Be sure 115 volts is supplied

to the transformer primary then
check for 24 volts at secondary
terminal before replacing.

9. Check and tighten all wiring

connections.

10. Replace.

1. Reset manifold pressure.

Refer to operation.

2. Replace regulator section of

combination gas valve or
complete valve.

3. Check with local gas supplier

for proper orifice size and
replace. Refer to operation.

1. Close air shutter. Refer to

Operation.

2. Check with local gas supplier

for proper orifice size and
replace.

1. Close air shutter. Open all

manual gas valves.

2. Reduce pilot gas. Refer to

operation.

3. Replace orifice.

4.

a. Reset manifold pressure
Refer to operation.
b. Replace regulator section of
combination gas valve or
complete valve.
c. Check with local gas sup-
plier for proper orifice size
and replace. Refer to
operation.

1. Open air shutters. Refer to

operation.

2. Clean main burner ports.
3. Replace manifold assembly.
4. Check for dust or lint at air

mixer opening and around the
air shutter.

5. Clean combustion air inlet

openings in bottom panel.
Refer to installation.

6. Clean draft hood/flue collecter.

Advertising