Technical data – Lenze 8400 motec Manual User Manual

Page 38

Advertising
background image

Technical data

Rated data
Operation with rated mains voltage 480 V

4

l

38

EDS84DG752 EN 4.0

Fuses and cable cross−sections

ƒ

Point−to−point connection − direct wiring of the mains voltage − typical fusing

Operation

Type

Installation according to EN 60204−1

1)

Installation according

to UL

2)

FI

3)



‚

L1, L2, L3 − laying system

ƒ

L1, L2, L3

B2

C

F

[A]

[A]

[mm

2

]

[mm

2

]

[mm

2

]

[A]

[AWG]

[mA]

E84DGDVB3714

C 16

16

2.5

15

12

³ 30

E84DGDVB5514

C 16

16

2.5

15

12

³ 30

E84DGDVB7514

C 16

16

2.5

15

12

³ 30

E84DGDVB1124

C 16

16

2.5

15

12

³ 30

E84DGDVB1524

C 16

16

2.5

15

12

³ 30

E84DGDVB2224

C 16

16

2.5

15

12

³ 300

E84DGDVB3024

C 16

16

2.5

15

12

³ 300

E84DGDVB4024

C20

20

4.0

20

12

³ 300

E84DGDVB5524

C20

20

4.0

20

12

³ 300

E84DGDVB7524

C 20

20

4.0

20

12

³ 300

ƒ

Multiple connection − loop−through connection of the mains voltage − maximum
fusing

Operation

Type

Installation according to EN 60204−1

1)

Installation according

to UL

2)

FI

3)



‚

L1, L2, L3 − laying system

ƒ

L1, L2, L3

B2

C

F

[A]

[A]

[mm

2

]

[mm

2

]

[mm

2

]

[A]

[AWG]

[mA]

E84DGDVB3714

C 32

32

6.0

15

12

³ 30

E84DGDVB5514

C 32

32

6.0

15

12

³ 30

E84DGDVB7514

C 32

32

6.0

15

12

³ 30

E84DGDVB1124

C 32

32

6.0

15

12

³ 30

E84DGDVB1524

C 32

32

6.0

15

12

³ 30

E84DGDVB2224

C 32

32

6.0

25

10

³ 300

E84DGDVB3024

C 32

32

6.0

25

10

³ 300

E84DGDVB4024

C 50

50

16.0

50

6

³ 300

E84DGDVB5524

C 50

50

16.0

50

6

³ 300

E84DGDVB7524

C 50

50

16.0

50

6

³ 300

1)

These values are recommendations only. Other dimensioning values/laying systems are possible (e.g. according to
VDE 0298−4). The cable cross−sections apply under the following conditions: Use of PVC−insulated copper cables,
conductor temperature < 70 °C, ambient temperature < 45°C, no bundling of cables or cores, three loaded cores.

2)

Only use UL−approved cables, fuses and fuse holders.
UL fuse: voltage

³ 500 V, tripping characteristic e.g. "CC". The cable cross−sections apply under the following

conditions: conductor temperature < 75 °C, ambient temperature < 45°C.

3)

Universal−current sensitive earth−leakage circuit breaker, short−time delayed

 Circuit breaker

‚ Fuse of gG/gL utilisation category or semiconductor fuses of gRL utilisation category

ƒ Fuse
Observe national and regional regulations