Informazioni sulla sicurezza

Altri pericoli

2

EDK84AZESRx DE/EN/FR/ES/IT 2.0

131

l

H1sic_IT−UR_COAs_Fe_Filter

O

Warnings !

Conditions of Acceptability:

ƒ

Appliance filters inherently have considerable leakage current to the
grounding conductor. The leakage current is to be measured in the end
product to determine compliance with the end use requirements.

ƒ

The filters shall be provided with an overall enclosure suitable for the
applicable end product requirements. Mounting means should be
considered in the end use application.

ƒ

These filters have been judged on the basis of the required spacings in the
Standard for Electromagnetic Interference Filters, UL 1283, Fifth Edition.

ƒ

The suitablity of the grounding means in conjuction with the filter, shall be
evaluated in the end use product.

ƒ

Electrical spacings between uninsulated dead metal parts should be in
accordance with the end use application.

ƒ

The components were submitted and tested with a maximum
manufacturer’s recommended ambient 45°C as indicated. Suitability of
these devices for use in a higher ambient needs to be determined in the
end use application.

ƒ

The suitability of filter leads, strain relief and lead terminations shall be
considered in the end use application.

ƒ

The Abnormal Operation Test (Par. 32, UL 1283), (limited short circuit test)
was not conducted. Suitability of this device to comply with this
requirement shall be considered in the end use application.