4technical data – Lenze E84AZESR RFI filter 3-29A User Manual

Page 46

Advertising
background image

4

Technical data

General data and operating conditions

EDK84AZESRx DE/EN/FR/ES/IT 2.0

46

l

H1_Daten−FE−Filt_84_Abmess_Tab

Operating conditions

Ambient conditions

Climatic

Storage

IEC/EN 60721−3−1

1K3 (−25 ... +55 °C)

Transport

IEC/EN 60721−3−2

2K3 (−25 ... +70 °C)

Operation

IEC/EN 60721−3−3

3K3 (−10 ... +55 °C)

Permissible
humidity

EN 61800−2

Humidity class 3K3 (without condensation;
average relative humidity 85 %)

Pollution

EN 61800−5−1

Degree of pollution 2

Site altitude

< 4000 m amsl
Above 1000 m amsl reduce the power by
5 %/ 1000 m.

Mechanical

Vibration resistance (9.81 m/s

2

= 1 g)

Transport

IEC/EN 60721−3−2

2M2

EN 61800−5−1

2 ... 9 Hz: amplitude 3.5 mm

10 ... 200 Hz: acceleration resistant up to 10 m/s

2

200 ... 500 Hz: acceleration resistant up to
15 m/s

2

Operation

Germanischer Lloyd

5 ... 13.2 Hz: amplitude ±1 mm
13.2 ... 100 Hz: acceleration resistant up to 0.7 g

EN 61800−5−1

10 ... 57 Hz: amplitude 0.075 mm

57 ... 150 Hz: acceleration resistant up to 10 m/s

2

Electrical

Mains connection

Power system

TT, TN

(with earthed neutral)

Operation is permitted without any restrictions.

IT

Operation is not permissible.

Mounting conditions

Mounting place

In the control cabinet

Mounting position

Vertical

Free space

^ 51