General data and operating conditions

Other application conditions

3

l

21

BA 13.0009 − EN 2.1

3.2

General data and operating conditions

Field

Values

Conformity

CE

Low−Voltage Directive (73/23/EEC)

Climatic conditions

Average relative humidity 85 %, without condensation

Admissible
temperature ranges

Designs

l

Non−ventilated or with
integral fan without brake or
with spring−applied brake

−20 °C ... +40 °C Without power reduction, over

+40°C with power reduction, see
catalog

l

With permanent magnet
brake

−10 °C...+40 °C

l

With separate fan, without
permanent magnet brake

−15 °C...+40 °C

Without power reduction

Mounting positions

Suitable for all mounting positions

Vertical arrangements in
accordance with DIN−IEC 34 Part 7
are possible if they meet the
designs

Enclosure

See nameplate

Enclosures only apply to horizontal
installation

Thermal class

F (155 °C) according to DIN−IEC 34 / VDE 0530

Exceeding the temperature limit
weakens or destroys the insulation

Tropical protection

Not guaranteed

Permissible installation
height h

h

£ 1000 m AMSL

1000 m AMSL < h

£ 4000 m

AMSL

Without power reduction
With power reduction, see catalog

Permissible voltage

1.5 kV peak value

5 kV/

ms rate of rise

Vibration

Up to 2.0g / 20m/s

2

without resonance excitation, e.g. of the fan.

3.2.1

Other application conditions

ƒ

Other application conditions require a power derating or torque reduction using the
factors listed in table 2 and 3 (see below).

3.2.1.1

Power derating

Data for power derating in the case of differing conditions

Cooling air temperature

°C

1)

40

45

50

55

60

Power derating k

υ

1)

1.00

0.95

0.90

0.83

0.77

Site altitude above amsl in m

2)

1000

2000

3000

4000

5000

Power derating k

h

2)

1.00

0.92

0.83

0.77

0.67

1)

Derating in the case of differing ambient or cooling air temperature

2)

Derating in the case of differing site altitude