Systems descriptions, Figure r – Braun RA500 User Manual

Page 35

Advertising
background image

Page 33

SYSTEMS DESCRIPTIONS

Computer Calibration Instructions for Controller

Introduction: The following procedure is for cali-

bration of the RA500 Series Controller. Calibrate

the controller only if ramp does not function

properly.

Electronic Controller can be calibrated using a

computer (recommended) or manually using the

onboard Calibrate button and potentiometers.

Computer Calibration procedures are provided for

Microsoft Windows XP. Other Operating Systems

may vary. Consult the operating system search

menu or users guide for alternate routes and proce-

dures to access port settings.

Electronic Controller

Connect the Computer to the Controller:

. Remove the controller cover. Press the “Cali-

brate” button and then the “Calibrate Reset”

button to restore factory defaults (see Figure S).

2. Locate J9 (9-pin Port) and connect a serial

cable from J9 to an available COM slot on the

computer.

Establish a connection between the computer

and the controller:

Note: This is done from the computer after the

physical connection has been made.

. In the start menu, go to “Programs” and select

“Accessories.”

2. Under “Accessories”, choose “Communica-

tions”, and then “Hyperterminal.” Once select-

ed, a “Connection Description” window will pop

up.

3 Under name: Enter “RA500” and hit OK. A

“Connect To” window will then pop up.

4. Under the “Connect Using” line, select the com

port that the serial cable is connected to (typi-

cally COM) and hit OK.

5. A window similar to the one in Figure R will

pop up. Ensure the settings match the settings

listed in Figure R. Press OK.

Bits per second:

Port Settings

Data bits:

Parity:

Stop bits:

Flow control:

8

None

None

1

19200

Restore Defaults

OK

Cancel

Apply

Figure R