Ti.274.275-06_pg2, Rohs, Technical information – MAMAC Systems PR-275 User Manual

Page 2: Low pressure sensor, Page 2 of 4, Typical applications (wiring diagrams)

Advertising
background image

Model PR-274/275

Technical Information

TI.274/275-06

LOW PRESSURE SENSOR

Page 2 of 4

PR-274/275 Low Pressure Transducer with mA Output

TYPICAL APPLICATIONS (wiring diagrams)

PR-274/275 pressure transducers with VDC output are field selectable 0-5 VDC

or 0-10 VDC output and can be powered with either a 12-40 VDC or 12-35 VAC.

The following describes the proper wiring of these pressure transducers with

VDC output:

Wiring PR-274/275 Units with VDC Output

1. Remove the terminal block by carefully pulling it off the circuit board.
2. Locate the [+], [-] and [O] terminal markings on the board.
3. Attach the power wires to the [+] and [-] terminals. The [-] terminal is also the

negative terminal.
4. Connect the [O] terminal, which is the positive VDC output terminal, to the

controller’s input terminal.

5. Re-insert the terminal block to the circuit board and apply power to the unit.
6. Check the appropriate VDC output using a voltmeter set on DC volts across

the [O] and [-] terminals.

PR-274/275 pressure transducers with 4-20 mA output are powered with a

12-40 VDC supply.

The following describes the proper wiring of these pressure transducers with

mA output:

Wiring PR-274/275 Units with mA Output

1. Remove the terminal block by carefully pulling it off the circuit board.
2. Locate the [+] and [-] terminal markings on the board.
3. Attach the supply voltage to the [+] lead.
4. Connect the 4-20 mA output ([-] terminal) to the controller’s input terminal.
5. Ensure that the power supply common is attached to the common bus of the

controller.

6. Re-insert the terminal block to the circuit board and apply power to the unit.
7. Check for the appropriate output signal using a DVM set on DC milliamps

connected in series with the [-] terminal.

PR-274/275 Low Pressure Transducer with VDC Output

TYPICAL APPLICATIONS (wiring diagrams)

Input Signal

+

Common

+

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

12-40 VDC Power Supply

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

Figure 1 and Figure 2 illustrate typical wiring diagrams for the mA output low

pressure transducer.

Figure 1 - Wiring for mA Low Pressure Transducers with an External DC Power

Supply

Figure 2 - Wiring for mA Output Transducers where the Controller or Meter has an

Internal DC Power Supply

Figure 3 and Figure 4 illustrate typical wiring diagrams for the VDC output low

pressure transducer.

Signal

+

Common

Supply

Neutral

Hot

O

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

VDC Output Transducer Only

12-35 VAC Transformer

Figure 3 - Wiring for VDC Low Pressure Transducers When Applied with External

AC Supply

Figure 4 - Wiring for VDC Low Pressure Transducers When Applied with External

DC Power Supply

Signal

+

Common

Supply

O

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

VDC Output Transducer Only

12-40 VDC Power Supply

S1
S2

Zu

Zb

S

+

0

S3

ON

ON

ON

MAMA

C

9280

High

Low

MAMAC

9280

MAMA

C

9280

MAMAC

9280

S1
S2

ON

ON

Zu

Zb

S

S1

S2

Zu
S

+

0

S3

ON

ON

Zb

ON

S1
S2

ON

ON

Zu

Zb

S

Caution: If you are using grounded AC, the hot wire must be on the [+] terminal. Also, if you are using a controller without built-in isolation, use an isolation transformer to supply the PR-274/275.

Caution: This product contains a half-wave rectifier power supply and must not be powered off transformers used to power other devices utilizing non-isolated full-wave rectifier power supplies.

Caution: When multiple PR-274/275 units are powered from the same transformer, damage will result unless all 24G power leads are connected to the same power lead on all devices. It is

mandatory that correct phasing be maintained when powering more than one device from a single transducer.

High

Low

Zb

Zu

S

Zb

Zu

S

Zu

S

Zu

S

Zb

Zb

RoHS

High

Low

High

Low

Advertising