LOW PRESSURE SENSOR

Page 4 of 4

CHECKOUT

CALIBRATION

1. Verify that the unit is mounted in the correct position.
2. Verify appropriate input signal and supply voltage.

3. Verify appropriate configuration range.

Caution: Never connect 120 VAC to these transducers. Never

connect AC voltage to a unit intended for DC supply.

Transducer

Operation

This is a rough functional check only.

1. Adjust the pressure to obtain maximum output signal for

appropriate range.

2. Output should be 20 mA or 5 or 10 VDC.
3. Adjust the pressure to obtain minimum output signal.
4. Output should be 4 mA or 0 VDC.

Calibration of PR-274/275 mA Units

1. Connect terminals [+] and [-] to the appropriate power

source.

2. Connect the DVM in series on the [-] terminal.
3. Apply low pressure to the unit. If configured for

uni-direction, adjust Zu trimmer to achieve desired low
output. If configured for bi-direction, adjust Zb trimmer to
achieve desired low output.

4. Apply high pressure to the unit and adjust span trimmer [S]

to obtain the desired high output pressure.

5. Repeat steps 3 and 4 until desired calibration is achieved.

All units are factory calibrated to meet or exceed published

specifications. If field adjustment is necessary, follow the

instructions below.

MAINTENANCE

Regular maintenance of the total system is recommended to

assure sustained optimum performance.

FIELD REPAIR

None. Replace with a functional unit.

WARRANTY

See Data Sheet for additional information.

Calibration of PR-274/275 VDC Units

1. Connect terminals [+] and [-] to the appropriate power

source. The [-] terminal is also the negative output terminal.

2. Connect the DVM on DC volts across [O] and [-] terminal.
3. Apply low pressure to the unit. If configured for

uni-direction, adjust Zu trimmer to achieve desired low
output. If configured for bi-direction, adjust Zb trimmer to
achieve desired low output.

4. Apply high pressure to the unit and adjust span trimmer [S]

to obtain the desired high output pressure.

5. Repeat steps 3 and 4 until desired calibration is achieved.

Figure 7 - PR-274/275 Low Pressure Transducer Dimensions shown in inches

and millimeters (mm).

1.56"

(40 mm)

2.12"

(54 mm)

S1
S2

ON

ON

MAMAC

9280

Z

Zb

S

5.00" (127 mm)

2.25"

(57 mm)

4.50" (114 mm)

1.12"

(28 mm)

1.12"

(28 mm)

5.50" (140 mm)

3.00" (76 mm)

3.00" (76 mm)

3.25"

(83 mm)

2.50"

(

63.5 mm

)

4.00"

(102 mm)

5.00" (127 mm)

2.20"

(56 mm)

6.00" (152 mm)

RoHS

TI.274/275-06

NOTE: The PR-274/275 is a highly accurate device. For

applications requiring a high degree of accuracy, the use of

laboratory quality meters and gauges are recommended.

Panel

Mount

Enclosure

For Technical / Application Assistance call your nearest office

8189 Century Boulevard • Minneapolis, MN 55317-8002 • USA

800-843-5116 • 952-556-4900 • Fax 952-556-4997

[email protected] • www.mamacsys.com

EUROPE

4200 Waterside Centre

Solihull Parkway

Birmingham • West Midlands

B37 7YN • United Kingdom

01384-271113 • Fax 01384-271114

AUSTRALIA

4 Armiger Court, Unit 2

Adelaide • S.A.

5088 • Australia

08-8395-4333 • Fax 08-8395-4433

CANADA

675 Cochrane Drive

East Tower • 6th Floor

Toronto • Ontario

L3R 0B8 • Canada

905-474-9215 • Fax 905-474-0876

ASIA

1 Fullerton Road #02-01

One Fullerton

Singapore • 049213

65-31581826 • Fax 65-31581826

MAMAC Systems, Inc., reserves the right to change any specifications

without notice to improve performance, reliability, or function of our products.

Advertising
This manual is related to the following products: