Appendix a, additional microsentry™ features – MARVEL Scientific 6CARFM User Manual

Page 15

Advertising
background image

perature alarm will activate at 9°C = (4 [setpoint] + 3 [Ahi] + 2

[hysteresis])

5) Relative Low Temperature Alarm (ALO): The

number of degrees C colder relative to setpoint

that will initiate a low temperature alarm. Once

the compartment temperature exceeds the low temperature

alarm value, the control will delay AdL minutes before initiating

the alarm. See Alarm Delay section below for instructions to

set alarm delay. While ALo is displayed on the screen, press and

hold SET key to view the value of ALohi. To adjust the value, con-

tinue to hold SET then use the WARMER and COLDER keys until

the desired value is shown on the screen. Release the SET key to

confirm the new setting. Factory default value for ALo is -2.0°C.

Note: Setting ALo = 0 will disable the low temperature alarm.

No hysteresis value is added to ALo. For example, let setpoint =

4°C, and ALo = -3. The low temperature alarm will activates at

1°C = (4 [setpoint] + -3 [ALo])

6) Alarm Delay (AdL): The number of minutes the

compartment temperature must be outside the

range specified by Ahi and ALo before a tempera-

ture alarm activates. While AdL is shown on the screen, press

and hold SET key to view the value of AdL. To adjust the value,

continue to hold SET then use the WARMER and COLDER keys

until the desired value is shown on the screen. Release SET key

to confirm the new setting. Factory default value for AdL is 60

minutes.

7) Total Operating Time of the Condenser Since

the Last Cleaning (cnd): The operating time of

the condenser since the last cleaning. The control

monitors the operating time of the condenser fan to determine

when the condenser is in need of being cleaned. While cnd is

displayed on the screen, press and hold SET key to view the value

of cnd. The value shown is the number of weeks the condenser

has been operating. To reset cnd, continue to hold the SET key

then press and release the ON/OFF key.

When the control recommends the condenser be cleaned, a

reminder will be displayed on the screen (see Alarm Codes.) To

clear the alarm code, reset the value in cnd following the instruc-

tions printed above.

8) Keypad Lockout Feature (Loc): This feature is

used to prevent incidental changes to the set

point, or accidentally turning the unit off. While

Loc is displayed on the screen, press and hold the SET key. If

“No” is displayed, Lockout feature is off, and all keys

are enabled. If “Yes” is displayed, Lockout feature is

ON. The ability to turn the unit on and off, as well as the ability

to adjust setpoint will be disabled. To change the keypad lockout

setting, continue to hold the SET key, then use the WARMER and

COLDER keys to set the desired value.

APPENDIX A, ADDITIONAL MICROSENTRY™ FEATURES

Information Menu / Lockout Key

To access the information menu, press the SET key, and immedi-

ately release it.

In the information menu, a 2 or 3 digit code will be displayed

representing each entry in the information menu. The first code

displayed will be t1. With each sequential press and release of

the SET key, the following codes will appear in this order: t1, thi,

tLo, Ahi, ALo, AdL, cnd, and Loc.

To view the value of each code, press and hold the SET key after

the desired code is displayed. Additionally, the WARMER and

COLDER keys may be used to scroll through the menu. To exit

the information menu, press the ON/OFF key, or wait for several

seconds with no key presses.

1) Current Interior Temperature (tI): Press and

hold the “SET” key to display the current interior

temperature.

2) Maximum Stored Temperature (thi): While

thi is shown on the screen, press and hold the

“SET” key to display the maximum recorded

temperature. The temperature is updated every 5 minutes. To

reset the maximum temperature; continue to hold the SET key,

then press and release the ON/OFF key to reset the maximum

temperature. The maximum temperature will be reset to the

current compartment temperature.

It is recommended that thi be reset after the initial pull-down

(24 hours after power on) to clear any residual values.

3) Minimum Stored Temperature (tLO): While tLo

is shown on the screen, press and hold the “SET”

key to display the minimum recorded tempera-

ture. The temperature is updated every 5 minutes. Continue to

hold the SET key then, press and release the ON/OFF key to reset

the minimum temperature. The minimum temperature will

be reset to the current compartment temperature. It is recom-

mended that tLo be reset after the initial pull down (24 hours

after power on) to clear any residual values.

4) Relative High Temperature Alarm (Ahi): The

number of degrees C warmer relative to the

setpoint that will initiate a high temperature

alarm. Once the compartment temperature exceeds the high

temperature alarm value, the control will delay AdL minutes

before initiating the alarm. See Alarm Delay section below for

instructions to set alarm delay. While Ahi is displayed on the

screen, press and hold SET key to view the value of Ahi. To

adjust the value, continue to hold SET then use the WARMER

and COLDER keys until the desired value is shown on the screen.

Release the SET key to confirm the new setting. Factory default

value for Ahi is 2.0°C.

Note: Setting Ahi = 0 will disable the high temperature alarm.

The control’s 2°C Hysteresis value is automatically added to Ahi.

For example, let setpoint = 4°C, and Ahi = 3. The high tem-

15