Digital I/O Connections

Models FlexTest® IIm/GT/SE Controller Hardware

FlexTest IIm Controller Connections

199

Digital outputs

Digital outputs provide an optically isolated open collector/open emitter
output.

The digital outputs are controlled by the Digital Output process in the
MultiPurpose TestWare application. They can also be controlled manually
in the Station Manager application.

Each digital output connector located on the Digital I/O Access Panel
supports two channels.

Each digital output is an open collector/open emitter rated at 30 V DC max
at 50 mA max.

Connector pinouts

The pin connections for the digital inputs and digital outputs are the same. Each
“D” style connector supports two channels.

J3 - 4

9

4

Ext Voltage

+CH4

-CH4

common

External Device

Opto-

Coupler

Digital I/O
Access Panel

498 Digital I/O
Transition Module

This figure shows how to

connect to an external

circuit using an external

power supply.

4

5

8

9

2

1

2

6

7

1

3

+12 V DC

+12 V DC

12 volt common

12 volt common

–Odd Channel #

–Even Channel #

+ Odd Channel #

+ Even Channel #

For example, the pins

associated with channels 1

and 2 are outlined.

The 12 volt supply is

reserved for the digital

inputs and should not be

used to power external

devices (it is rated for

maximum 250 mA current).