5a. MAKE ELECTRICAL CONNECTIONS. CONNECT

GROUND WIRES TO GREEN GROUND LEADS.

CONNECT WHITE (COMMON) TO WHITE LEADS.

CONNECT POWER SUPPLY (LINE) TO BLACK

LEADS.

WARNING: DO NOT PINCH WIRES. CONSULT A

QUALIFIED ELECTRICIAN FOR ALL OTHER

OPTIONS THAT REQUIRE OTHER WIRING

CONFIGURATIONS.

5b. (DIMMING ONLY) CONNECT GRAY AND VIOLET

WIRES (SEE STEP #4b). DIMMING WIRE CONNEC-

TION MUST NOT BE MADE WITHIN BALLAST

HOUSING TO RETAIN CLASS 2 RATING FOR THE

DIMMING WIRES. MAKE THIS CONNECTION ONLY

AFTER PERFORMING STEP #4b.
IMPORTANT:

DIMMING FIXTURES: 0-10 VOLT CONTROL ONLY.

6. PUSH SLICES INTO THE BALLAST HOUSING.
7. FASTEN 2 HEX SCREWS (SUPPLIED) HALFWAY

INTO PENDANT BRACKET HOLES.

8. ASSURE THAT RETAINER RING IS PUSHED DOWN

OVER BALL HALVES AND SNAPPED INTO COVER

PLATE (PENDANT).

12. INSTALL THE DESIRED REFLECTOR AFTER ALL

CEILING INSTALLATION AND FINISHING WORK IS

COMPLETE.

*SEE INSTRUCTION SHEET 1077-**** FOR DPR8 &

DPR10 SERIES REFLECTORS.

*SEE INSTRUCTION SHEET 1079-**** FOR DPRL &

DPRVML SERIES DIFFUSERS.

13. INSTALL THE DESIRED LAMP (BY OTHERS)
INSTRUCTIONS FOR LAMP POSITIONING

THERE ARE 3 LAMP POSITIONS AVAILABLE FOR

THIS FIXTURE. THE FIXTURE IS SHIPPED AND

INSTALLED IN THE LOWEST (CLOSEST TO

REFLECTOR APERTURE) POSITION.THESE

POSITIONS ARE DETERMINED BY AN

ADJUSTABLE BRACKET MECHANISM WITHIN THE

HOUSING. THE 57W VERSION ONLY HAS ONE

LAMP POSITION AVAILABLE.

14a. IF THE LAMP IS A 26W COMPACT FLUORESCENT,

DO NOT REPOSITION THE LAMP.

14b. IF THE LAMP IS A 32W COMPACT FLUORESCENT

LAMP, PLACE THUMBS AT BOTTOM OF LAMP AND

PUSH UP UNTIL BRACKET MECHANISM CLICKS

INTO MIDDLE POSITION.

14c. IF THE LAMP IS A 42W COMPACT FLUORESCENT

LAMP, PLACE THUMBS AT BOTTOM OF LAMP AND

PUSH UP UNTIL BRACKET MECHANISM CLICKS

INTO TOP POSITION.

15. TO REPOSITION THE LAMP TO A LOWER

POSITION, PULL DOWN ON THE CHAIN SHOWN

IN THE LOWER FIGURE. PUSH ON LAMP UNTIL IT

IS IN THE NEW POSITION (SEE STEPS 14a - 14c).

9.

HOLD PENDANT UP TO HOUSING FIXTURE,

ALLOWING CEILING COVER TO REST AT BOTTOM

OF STEM. CONNECT THE MATE-N-LOCK

CONNECTOR FROM THE HOUSING FIXTURE TO

THE CONNECTOR FROM THE PENDANT.

10. PASS MATED CONNECTORS THROUGH SLOT OF

PENDANT BRACKET AND ALIGN HOLES OF

MOUNTING PLATE TO HEX SCREWS ON

PENDANT BRACKET. TURN MOUNTING PLATE

COUNTERCLOCKWISE AND TIGHTEN HEX

SCREWS.

11. MATE CEILING COVER TO HOUSING FIXTURE

HOLE AND INSERT TORSION SPRINGS THROUGH

SLOTS (SEE DETAIL “B”).

TORSION

SPRING

REFLECTOR NOT SHOWN FOR

EASE OF VIEW

CHAIN

SEE PAGE 3 FOR FIGURE OF FULLY INSTALLED FIXTURE

SLOT FOR TORSION

SPRING (2X)

CEILING

COVER

DETAIL “B”

(FOR STEP #11)

RETAINER

RING

STEM AND

PENDANT

COVER

PLATE

BALL HALF