Appendix a, Technical specifications, Appendix a technical specifications – SATEC EM132-133 Manual User Manual

Page 126: A.1 environmental conditions, A.2 construction, A.3 three phase power supply – em133-se, A.4 auxiliary power supply

Advertising
background image

‎Appendix A Technical Specifications

126

EM13x Series SMART MULTIFUNCTION METER

Appendix A Technical Specifications

A.1

Environmental Conditions

Operational ambient temperature limit range: –25

C to +60

C

Specified ambient temperature range: –20

C to +60

C

Long-term damp heat withstand according to IEC 68-2-3 <95% (non
condensing), +40

C

Transport and storage temperature range: –30

C to +85

C

IEC 60068-2-6, AS 60068-2-6 [18]: Vibration

Frequency range: 10Hz to 150Hz

Vibration time (each axis): 75 min

Sweep rate: 1 oct/min

Max Vibration level: 10 m/s

2

(1g), f > 60Hz

IEC 60068-2-27, AS 60068-2-27 [19]: Shock

Shock level: 30 g

Time duration: 18 ms

Shape: Half sine

Number of shocks: 18

A.2

Construction

Case enclosure: Reinforced Polycarbonate

Packaging case: Carton and Stratocell® (Polyethylene Foam) brackets

Labels: Polyester film (UL94-V0)

A.3

Three Phase Power Supply – EM133-SE

Indirect Connection

Rated input from 1, 2 or 3 phases: 3 x 120-277 VAC 50/60Hz Burden 2VA
per phase

Direct Connection

Rated input from 1, 2 or 3 phases: 3 x 120-230 VAC 50/60Hz Burden 2VA
per phase

Isolation:

Input to ground: 4000V AC

Wire size: up to 12 AWG (up to 3.5 mm2)

A.4

Auxiliary Power Supply

Rated input: 40-300VAC 50/60Hz, 40-300VDC, Burden 5VA

Frequency range operation 25-400 Hz

Isolation:

Input to ground: 4000V AC

Wire size: up to 12 AWG (up to 3.5 mm2)