‎Chapter 5 Configuring T H E E M 1 3 X S E R I E S

62

EM13x Series SMART MULTIFUNCTION METER

To change the port settings in your device, select desired port
parameters, and then click Send.

The following table lists available port options.

Table 3: COM Port Options

Display Label

Parameter

Options

Default

Description

Protocol

Communication

protocol

MODBUS RTU,

MODBUS ASCII,

DNP3, SATEC ASCII,

IEC 60870-5

MODBUS RTU

(COM 1-3)

The

communications

protocol for the

port

Interface

Port interface

RS485, RS232, IR,

GPRS, ETHERNET,

PROFIBUS

RS485 (COM1)

RS232 (COM2)

IR (COM3)

Not changeable;

automatically

detected by the

meter

Address

Device address MODBUS: 1-247

DNP3: 0-65532

IEC 60870-5: 1-4095

1

Device network

address

Baud Rate

Baud rate

COM1: 300-115.2
kbps,

COM2: 300-115.2

kbps

COM3: 9600-38400

kbps

19.2 kbps

The port baud rate

Data/Parity

Data format

and parity

7E, 8N, 8E

8N

7E data format

should not be used

with the MODBUS

RTU and DNP3

protocols

Send Delay

Response delay 0-1000 ms

5 ms

The minimum time

after the last

request character

is received to start

the transmission.

Chr.Timeout

Character

timeout

0-1000 ms

4 ms

The maximum time

the line is allowed

to idle before

closing a

connection in the

MODBUS RTU and

DNP3 protocols

The meter automatically detects replaceable communication modules
and does not allow you to change the baud rate and data format for
the Dial-up GSM/GPRS modem.