Chapter 8 Configuring Recorders

Configuring the Fault Recorder

108

SA300 Substation Automation Unit

3. If you wish to change the default settings, adjust thresholds and

hysteresis for your fault triggers.

4. Select the waveform and data logging options for fault events.
5. Download your setup to the device.

The following table lists available Fault recorder options.

Option Range

Default

Description

Thresholds

Threshold, %

0-200.0%

Defines the operating threshold for the fault trigger in
percent of the nominal (reference) value

Threshold,

secondary

Shows the setup value in secondary units for the

selected operating threshold

Hysteresis, %

0-50.0%

5.0

Defines the hysteresis for fault trigger in percent of the
threshold

Trigger Enabled Checked

Unchecked

Checked

Links the fault trigger to the Fault Recorder. If the box

is leaved unchecked, the Fault Recorder does not
respond to the trigger.

Waveform Log

On Start

Checked
Unchecked

Checked

Enables waveform log when the fault event starts

On End

Checked
Unchecked

Unchecked Enables waveform log when the fault event ends

Log No.

1-8

7

Specifies the waveform log file used for waveform

recording on the fault event

1/2-cycle RMS Plot

Log Enabled

Checked
Unchecked

Unchecked Enables concurrent RMS trace plot to the data log file

while the fault event continues

Max. Duration

0-10,000 cycles 100

Maximum duration of the 1/2-cycle data trend log. The
logging is stopped automatically when either a fault
event ends or the specified number of cycles has been
recorded.

Before, Cycles

0-20 cycles

4

The number of cycles to be recorded prior to the event

After, Cycles

0-20 cycles

4

The number of cycles to be recorded after the event

Log No.

13

13

Specifies the data log file used for data recording on
the fault event

To enable or disable the Fault recorder in your device:

1. Check or uncheck the “Recorder Enabled” checkbox.
2. Send the new setting to the device.

In IEEE 1159 versions, current and voltage faults detected by the Fault recorder are
normally recorded into the IEEE 1159 Power Quality log file. To disable this option:

1. Uncheck the “Record to PQ Log” checkbox.
2. Send the new setting to the device.

Configuring Analog Triggers

Voltage and current thresholds are normally specified as a percent of a nominal
(reference) voltage and current. The voltage reference is the line-to-neutral PT
secondary voltage for the 4LN3, 3LN3 and 3BLN3 wiring configurations, and the line-
to-line PT secondary voltage for other wiring configurations. The reference value for

current triggers is the CT secondary current rating for the extended range current
inputs. See

Basic Device Setup

in Chapter 7 for information on specifying voltage

and current ratings in your device.

To make easier specifying thresholds for voltage and current triggers, PAS also
shows you threshold values in secondary units that match the percentage you

selected for the triggers. To update the thresholds in secondary units, type the
threshold for a trigger in percent, and then press Enter or click elsewhere on the Fault
Recorder setup tab.