Chapter 8 Configuring Recorders

Configuring the IEEE 1159 Power Quality Recorder

94

SA300 Substation Automation Unit

The available PQ recorder options are shown in the following table:

Option Range Default

Description

Thresholds

Threshold, % 0-200.0%

Defines the operating threshold for the PQ trigger in
percent of the nominal (reference) value

Hysteresis, % 0-50.0%

5.0

Defines the hysteresis for PQ trigger in percent of the
threshold

Waveform Log

On Start

Checked
Unchecked

Checked

Enables waveform log when the PQ event starts

On End

Checked
Unchecked

Unchecked Enables waveform log when the PQ event ends

Log No.

1-8

7

Specifies the waveform log file used for waveform
recording on the PQ event

Data/RMS Plot

Enabled Checked

Unchecked

Unchecked Enables concurrent RMS trace plot to the data log file

while the PQ event continues

1/2-cyc

0-10,000 cycles

30

Duration of the 1/2-cycle data trace

0.2-sec

0-10,000 seconds 3

Duration of the 0.2-second data trace

3-sec

0-10,000 minutes 3

Duration of the 3-second data trace

10-min

0-10,000 hours

0

Duration of the 10-minute data trace

Before, Cycles 0-20 cycles

2

The number of cycles to be recorded prior to the event

After, Cycles

0-20 cycles

2

The number of cycles to be recorded after the event

Log No.

14

Specifies the data log file used for data recording on
the PQ event

The Sag, Swell and Interruption triggers use the same waveform and data log
options. If you change one of them, the others are automatically adjusted to the same
setting.

The waveform log option allows recording waveforms both at the start and the end of

a PQ event. Since the voltage variations may last from some seconds to minutes, this
allows capturing and analyzing the voltage transitions using short time waveform
recording at the start and the end of the voltage sag or swell.

The data log option allows concurrent recording of the RMS data at a variable rate
depending on the PQ event duration. To reduce the memory consumption for

recording long duration events, the PQ recorder uses different time envelopes
(aggregation intervals) for data tracing and changes the recording rate accordingly.