Setting the Communications

You communicate with the meter via a changeable COM1 communication port, or

through a second factory set serial RS-485/RS-422 COM2 port. Depending on

what was ordered, the COM1 port is equipped with an RS-232/RS-422/RS-485

serial interface, with a dial-up modem for communicating through public telephone

lines, or with an Ethernet module for communicating through the Internet.
To configure the PM175 communication via PAS:

1. Select Configuration from the Tools menu. Under the

Communication group of the Instrument Setup tab, select the

type of a connection for your device.

2. Enter the device communication address you assigned to the

PM175.

3. In the Sampling Rate box, select a rate at which PAS updates

data on your screen when you continuously poll the device in

the PAS Data Monitor.

The communication protocol and port settings in PAS must match the settings

made in your device.

COM1 Settings

Code

Parameter

Options

Description

Prot

Communications protocol

ASCII, rtu*, dnP3

ASCII, Modbus RTU or DNP3.0 protocol

rS

Port Interface, depends on

order

232 = RS-232
485 = RS-485
422 = RS-422
dial = Dial-up Modem

Eth.= Ethernet

For non-serial interfaces this is not changeable,

it is automatically detected by the meter

Addr

Device Address

Modbus: 1 (default) -247
DNP3.0: 0 (default) -255

bAud

Baud rate

300 - 115,200 bps (19,200 bps*)

dAtA

Data format

7E, 8E (7/8 bits, even parity), 8N* (8 bits, no parity)
7E data format should not be used with the Modbus RTU and DNP3

protocols

H.Sh

Handshaking (flow control)

nonE*=no flow control
SOFt=software (XON/XOFF)
HArd=hardware (CTS)

rtS

RTS mode

nonE* = not used
Forc = RTS is permanently asserted
CtrL = RTS is asserted during the transmission

COM2 Settings

Code

Parameter

Options

Description

Prot

Communications protocol

Rtu* = Modbus RTU
ASCII = Modbus ASCII
dnP3 = DNP3

The communications protocol supported by the

port

rS

Port Interface

485* = RS-485
422 = RS-422

Addr

Address

Modbus: 1*-247
DNP3: 0–65532

Device network address

bAud

Baud rate

300-115,200 bps

(19,200 bps*)

The port baud rate.

dAtA

Data format and parity

7E, 8N*, 8E

7E data format should not be used with the

Modbus RTU and DNP3 protocols

BG0456 REV.A2

11