PM175 Quick Start Guide

The typical installation diagram above shows a 4-Wire Wye 2½-element

connection using 2 PTs and 3 CTs. The wiring mode is 3LL3 or 3Ln3. The voltages

must be balanced for the configuration to provide accurate power measurements.
There are approximately nine different wiring configurations in the PM17X Series.

Refer to the Installation and Operational Manual for additional configurations.
For electrical installation of the display panel follow the following steps:

1. Connect the remote display using the pinout tables below,

either for a self-powered display or a remote powered display.

Refer to the Installation and Operation Manual for the wiring

schematic diagrams.

Pinout for a self-powered remote display

PM175
D15 Female
Pinout

Signal

Remote

Display
D15 Male
Pinout

1

+12V

1

5

RS-485 + (plus)

5

7

RS-485 - (minus)

7

8

GND

8

15

Chassis

15

Pinout for a remote display powered from an external 12V DC,

350 mA power source

PM175
D15 Female
Pinout

Signal

Remote

Display
D15 Male
Pinout

1 N.C.

+12V

1

5

RS-485 + (plus)

5

7

RS-485 - (minus)

7

8 N.C.

GND

8

15

Chassis

15

2. Connect the DC or AC power.
3. Connect the chassis ground.
4. Connect the required wiring configuration.
5. Connect the I/O connections as required. For I/O ratings, see

the Technical Specifications section in the Installation and

Operation Manual.

Using the Navigation Buttons