PM175 Quick Start Guide

To change the option:

1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the desired

option.

3. Press ENTER to confirm your changes and to store your new

setting, or press ESC to discard changes.

4. Press ESC to exit the menu.
The table below lists the available options.

Label Parameter

Options

Default Description

ConF

Wiring connection

(configuration) mode

3OP2
4LN3
3DIR2
4LL3
3OP3
3LN3
3LL3
3BLN3
3BLL3

4Ln3

The wiring connection of the device

Pt

PT ratio

1.0-6500.0

1.0

The phase potential transformer’s

primary to secondary ratio

Pt.F

PT Ratio multiplier

Ч1, Ч10

Ч1

PT Ratio multiplication factor. Used

in extra high voltage networks to

accommodate the PT ratio for 500

kV and higher networks.

U.SEC Nominal secondary

voltage

10-690 V

120 V

The nominal secondary line-to-

neutral (in configurations with a

neutral wire) or line-to-line voltage

(in 3OP2, 3OP3 and 3DIR modes)

voltage. Used as a reference

voltage for the EN50160 evaluation.

Ct

CT primary current

1-20,000 A

5 A

The primary rating of the phase

current transformer

d.P

Power block demand

period

1, 2, 3, 5,

10, 15, 20,

30, 60 min,

E=external

sync

30 min

The length of the demand period for

power demand calculations. If the

external synchronization is selected,

a pulse front on the digital input

DI1 denotes the start of the

demand interval.

nd.P

The number of

blocks in the sliding

window

1-15

1

The number of blocks to be

averaged for sliding window

demands

Ad.P

Ampere, volt and

THD demand period

0-1800 sec

900 sec The length of the demand period for

ampere, volt and THD demand

calculations

Freq

Nominal frequency

50,60 Hz

60 Hz

The nominal line frequency

LoAd

Maximum demand

load current

0-10000 A

0

The maximum demand load current

(0 = CT primary)

Always specify the wiring mode and transformer ratings prior to setting up setpoints and analog outputs.

The maximum value for the product of the phase CT primary current and PT ratio is 57,500,000. If the product is

greater, power readings are zeroed.