PM175 Quick Start Guide

Figure 9: PM175 Navigation buttons

Setup is performed directly from the display panel or via the communication ports

using PAS communication software.
In Data Display mode, the navigation buttons function as follows.
The MIN/MAX button switches to the Min/Max Maximum Demands display pages.

When briefly pressed again, it switches back to the common measurements

display.
The PQ/ESC button switches between different power quality/harmonic displays:

Total Harmonics, Individual Voltage and Current Harmonics, and Power Quality

parameters – short-term (Pst) and long-term (Plt) flicker, and voltage and current

negative sequence unbalance. When briefly pressed once again, it switches back

to the common measurements display.
The UP and DOWN arrow buttons, labeled by arrowheads, scroll forwards and

backwards through the display pages. Pressed briefly, they move one page

forward or backward. If you hold the button down, the display pages are scrolled

at rate of a twice per second.
Pressing both the UP and DOWN arrow buttons together returns to the first page

within the current display.
The SELECT button operates once it’s released. The button has two functions:

o

When pressed briefly, switches to programming mode.

o

When pressed together with the ENTER button for more than

5 seconds, it resets Min/Max records, maximum demands, or

energies depending on the currently displayed page. If the

meter is password protected, and a simple reset of data from

the display is not allowed, the action has no effect.

The ENERGY/ENTER button switches to the Energy display. If TOU registers are

configured in the meter, you can repeatedly press this button to scroll through all

available TOU registers. When briefly pressed once again, it switches back to the

common measurements display

Auto Return
If no buttons are pressed for 30 seconds while the display Auto Return option is

enabled, the display automatically returns to the main screen from any other

measurement display.
The Auto Return option is enabled through the Display Setup menu

Auto Scroll
If no buttons are pressed for 30 seconds while in the common measurements

display, and the Auto Scroll option is enabled in the meter, the display

automatically scrolls through all available pages. The scroll interval is adjustable in

the Display Setup menu.
To stop auto scrolling, briefly press the SCROLL button.