1 ABOUT THE COMMUNICATION DRIVER


The driver provides data exchange between SLC 5/02, 5/03 and 5/04 modular controllers, and
SATEC Powermeters via the 1746-BAS BASIC module.

The EPROM firmware versions can be supplied for 1 to 31 instruments. Three data sets and
three baud rates (1200, 2400 and 9600 baud) are available upon order. For available data sets,
refer to Appendix A.

The driver supports all models of SATEC Powermeters, although certain parameters might

not be relevant to some models, and in this case will be transmitted as zeroes.

The time required for polling one instrument and processing the acquired data until the data

transfer to the SLC CPU occurs is 5 to 7 seconds, depending on the model of the instrument
being polled.

The instruments are connected to the BASIC module's PRT2 port that is configured as ASCII

interface port. The PRT2 port can be configured for RS-422, RS-485 or RS-232
communication. When using RS-232 interface, only one Powermeter may be connected to the
BASIC module. With RS-422/RS-485 communications, up to 31 instruments can be connected to
the BASIC module in multidrop mode.