4. PRE-INSTALLATION SURVEY

The ATH / IA heating system must be supplied by gas piping of the correct diameter, length,
and arrangement to function properly. For this reason, a layout drawing is necessary. Carefully
survey area to be heated, for best results. Whenever possible, place burner and combustion
chamber in coldest area.

5. MOUNTING CLEARANCES

This heater must be mounted with minimum clearances between the reflector surface and
combustibles as shown in FIGURE 1 (page 5) TABLE 3 (page 5).

For recommended heater placement refer to TABLE 2 (below). Heaters should also be located
with respect to building construction and equipment so as to provide a minimum clearance of
24 inches from the end of burner housing to allow for servicing and cleaning of burner, blower
and controls.

TABLE 2 RECOMMENDED HEATER PLACEMENT FOR POULTRY BROODING


MODEL

RECOMMENDED

MOUNTING

HEIGHT

MINIMUM

MOUNTING

HEIGHT

MAXIMUM

MOUNTING

HEIGHT

ATH / IA 130

9’

65"

120"

ATH / IA 110

8’

60"

108"

ATH / IA 80

7’

54"

96"

ATH / IA 60

7’

48"

84"

ATH / IA 45

7’

45

84”

IMPORTANT

: Continuous operation of single or multi-heater placement must not

cause any combustible material in storage to reach a temperature
in excess of 160

O

F.