Chapter 2: installation

CONFIGURING THE ALARM RECOGNITION TIME
Set the Alarm Recognition Time for each zone input by setting the

DIP Switches according to the table below.

Switch A

Switch B

3 seconds

Off

Off

1 minute

Off

On

5 minutes

On

Off

10 minutes

On

On

TESTING THE SYSTEM
Check that all equipment being monitored is operating normally

and press the Alarm Status pushbutton. All 4 LEDs should light

up green. If an input is in an Alarm condition and has met the

recognition time the LED will light up red. Verify that the LEDs

display correctly under both Normal and Alarm conditions. Make

and hold an alarm to test the alarm delivery process. You must

maintain the alarm condition until all telephone calls have been

received. Once the alarm clears, the dial-out process is cancelled.