Sensaphone 800 User Manual

Page 101

Advertising
background image

Chapter 7: Operation

99

Call Delay:
Expired

Intercall Time:
Activated

Voice Repetitions:
Activated

Call Progress:
Activated

Max Calls:
Activated

Alarm Messages:
By Telephone
and
On site

III . Dial-out Begins

Variable Factors

• The dial-out process is activated as soon

as the Call Delay time expires (if the
alarm has not been cancelled at the Model
800’s installation site.) The dial-out begins
with telephone number 1 and proceeds
sequentially, through the remaining
telephone numbers.

• If the alarm is not acknowledged with the

first dial-out telephone call, the Model
800 waits the duration of Intercall Time
before dialing the next telephone number.
Intercall Time is the programmed waiting
period in between each dial-out telephone
call.

• When the telephone is answered, the

programmed Voice Repetitions determine
the number of times per call the Model
800 recites the alarm message.

• Call Progress, an automatic feature,

enables the Model 800 to detect whether
or not the telephone call is answered. After
10 rings, or if a busy signal is encountered,
the Model 800 will hang up, wait the
programmed Intercall Time, and proceed
to dial the next telephone number.

• If no telephone calls are answered, the

Model 800 dials out sequentially, through
the remaining telephone numbers and
continues to cycle until the programmed
Maximum Number of Calls is reached.

• When the telephone is answered, the

Model 800 will immediately begin reciting
a message that indicates which of the
zones is in alarm. At the same time, the
alarm message is repeating at the Model
800’s installation site. The Model 800 will
request acknowledgment, if it has not yet
occurred.

Advertising