P O W E R M O N I T O R P A C K A G E O N L Y

POWER MONITOR OPTION

HG7 I, O, & M Manual

24

Product Technical Specifications

Table 3 lists the major technical specifications for the HG7 “XM” Option filter product:

Table 3 – HG7 “XM” Option Harmonic Filter Technical Specifications

Voltage ratings

240, 480 and 600 V, 3 ph, 60 Hz
380 – 415 V, 3 ph, 50 Hz

kVar ratings

3 to 120 kVar, 140 to 270 kVar depending on voltage.

Load types

3-phase diode bridge rectifier loads such as PWM AC drives

Load power range

7.5 - 400 HP, 500 - 900 Hp depending on voltage. See Rating and
Dimension tables.

Current ratings

The included series reactors can tolerate 200% of rated current for at
least 3 minutes.

SCCR (short circuit current
rating)

Standard rating is 10kA.

Maximum elevation

3,000 feet (1,000 meters) as standard. Product must be equipped with
special cooling provisions for operation above this altitude.

Maximum ambient operating
temperature

50°C (122°F) – Open Panel; 40°C (104°F) – Enclosed Panel.

Product must be equipped with special cooling provisions for
operation above this temperature.

Maximum ambient storage
temperature

60°C (140°F)

Maximum humidity,
operating or storage

95%, non-condensing.

Enclosure options

Standard: UL Type 1 enclosure

Agency approvals or
certifications

UL and cUL Listed to UL508A and CSA-C2.2 No. 14

Insertion Impedance

+/- 10% at full load current

Fusing and protection:

All units have internal fuse protection for the harmonic filter.
HG2 Protection Monitor is standard in units rated over 20 kVar.

LCD display
(units with HG2 Monitor)

Operating Parameter values: kW, kVA, power factor, voltage,
current, harmonic voltage, current, and total harmonic distortion

Faults: low current trip, high current trip, time delay over-current trip,
door interlock, over-temperature, multi-unit external, and interlock
faults.
Setup Parameters: filter nameplate ratings, fault & reset delays, and
trip levels.

Status indication LEDs
(units with HG2 Monitor)

Green LED indicates: Filter Enabled
Red LED indicates: Filter Disabled

Fault relay
(units with HG2 Monitor)

De-energized when a fault is detected.
Form C contact for customer use; rated 5 A at 120 VAC & 5 VDC.

Pilot lights
(Units w/o HG2 monitor)

Blown Fuse indicating lights for 3-phase filter fuses
Filter Enabled pilot light

Capacitors

Oil filled high endurance design (no PCBs)