About Advanced Features & Operation

Page 16

2 STAGE OPERATION - The 2nd Stage of heat or cool is
turned on when (1) the 1st Stage has been on for a
minimum of two minutes, and (2) the temperature spread
from the setpoint is equal to or greater than: the setpoint
plus the deadband, plus 2 degrees.

Heat

Setpoint

Cool

Setpoint

Dead
Band

Dead
Band

2 degrees

2 degrees

1st Stage

turn on

2nd Stage

turn on

1st Stage

turn on

2nd Stage

turn on

Heating

Cooling

MINIMUM HEAT/COOL SETPOINT DIFFERENCE - The Heat
and Cool setpoints will not be allowed to come any closer
to each other than the value set in Advanced Setup step
# 7, on page 13. This minimum difference is enforced
during Auto changeover

operation.