Burnham Indirect - Fired Water Heater AL SL User Manual

Page 6

Advertising
background image



q

Do not apply heat directly to the cold-water inlet as it is made of plastic and will melt.

G. BOILER SUPPLY CONNECTIONS

q

WARNING: Boiler temperature must be controlled by the boiler high limit not to exceed 200°.

Failure to do so will create a hazardous installation and void the applicable limited warranties.

q

All water supply fittings on this heater are brass – do not over tighten or strip threads.

q

It is recommended to use a union as per Figures 1 and 2.

NOTE: Be sure to connect Boiler Supply Line (from the boiler) to the “HX in” fitting and Boiler

Return Line (to the boiler) to the “HX Out” fitting.

H. FILLING THE HEATER

q

Check that the temperature-and-pressure relief valve has been properly installed (mandatory

requirement).

q

Completely close the drain valve.

q

Open the highest hot water faucet to allow air to escape from piping.

q

Open the valve to the cold-water inlet and allow the heater and piping system to completely fill, as

indicated by a steady flow of water from the open faucet.
I. TPI THERMOSTAT INSTALLATION

q

Attaching TPI Thermostat to tank:

Place hole in back of TPI thermostat over immersion well. TPI thermostat should fit flush against the

tank without immersion well protruding beyond cover of TPI case. Use self-tapping screw provided

(Screw A) to attach TPI directly to the Alliance SL tank. (See TPI Diagram )

q

Inserting the Temperature Sensor:

Slide temperature sensor all the way into the immersion well – until it contacts the end.

(See TPI Diagram )

q

The sensor will measure temperature adequately by resting against the bottom of the immersion

well.

(Note: Sensor does NOT need to make intimate contact with entire well surface to work properly)

CAUTION: Sensor is soldered directly to TPI. DO NOT BEND SHARPLY OR OVERWORK.

J. TPI WIRING CONTROLS
NOTE: THE TPI CONTROL ELECTRONICS MUST BE POWERED WITH 4VAC.

q

Incoming 24VAC power must be connected to 24VAC connectors on the bottom right corner of TPI

Thermostat.

(See TPI Diagram 3)

q

The TPI 24VAC only requires 20mA, or about 0.5 Watts.

q

Connect control wiring to PUMP/TT normally open relay connections (rated for both 24V and 110V

wiring) on the bottom left corner of TPI control.

(See TPI Diagram 3)

q

TPI Wiring will vary depending on the type of boiler and valve controls in the system. Consult

attached Wiring Diagrams for appropriate wiring configuration for your system.

q

The Alliance SL water heater may operate as a separate heating zone using either the heating

system circulator and an appropriate zone valve, or a separate circulator dedicated for water heating.

(See Figure  & ).

q

In both systems, the Alliance SL is controlled through the TPI thermostat on the heater.

(See Figures 1 & 2).

q

TPI thermostat calls for the heat when the temperature in the tank is below the set point (120°F) and

either activates a circulator or zone valve depending upon installation design.