PowerFlex 700 with Vector Control Option Custom Firmware 11

Rockwell Automation Publication 20B-IN020C-EN-P - January 2014

676

Counter for position reconnect

677

Pump status:

bit 13 = Pump off disable input active
bit 12 = 0 = Position, 1 = Cycle torque used
bit 11 = 1 = Top of stroke
bit 10 = Position initialization active
bit 9 = Sleep mode enabled
bit 8 = Sleep is active, drive is stopped
bit 7 = Position initialization storing values
bit 6 = Detected upstroke
bit 5 = Detected downstroke
bit 4 = Pump off control active and external disable input off
bit 3 = Not used
bit 2 = Drive is at commanded speed
bit 1 = Upstroke
bit 0 = Downstroke

678

State of position detector (1…6) and reconnect (7…14)

679

Torque used to slope detection

680

Heavily filtered torque used for position detection

682

Filter level for above, can be changed

683

Stored values of position 1 for reconnect

684

Stored values of position 2 for reconnect

685

Stored values of position 3 for reconnect

686

Stored values of position 4 for reconnect

687

Stored values of position 5 for reconnect

688

Top of stroke position

689

TRUE if pump off stop enable and PO occurred

690

Used to detect stop while sleeping

691

Parameter 684 – Pump Off Action

692

2ms counter used in Pump Off timing

693

Pump Off time in drive units

694

TRUE if initializing position

695

Amount of dither for position correction

699

Bus Limit Ki

700

Bus Limit Kp

704

Bus Limit Enable

705

Bus Limit reference

706

Time in msec for a stroke based on gear ratio

Test Points (cont.)

Test Point

Description